beautypg.com

Legrand WSP101 User Manual

Pass & seymour

background image

No: 341009 – 8/12 Rev. B

U.S. Patents: 5640113, 6617560

Pass & Seymour

®

Passive Infrared Wall Switch Occupancy Sensor

Détecteur de présence à infrarouges passif avec interrupteur mural

Sensor de ocupación con interruptor a la pared infrarrojo pasivo

Installation Instructions • Instrucciones de Instalación • Notice d’Installation

Catalog Number • Numéro de Catalogue • Le Numéro de Catalogue: WSP101, WSP201

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

CAUTION

Turn power off at the circuit breaker before installing

sensor or working on the load.

AVERTISSEMENT

Coupez l’alimentation du disjoncteur avant d’installer

le détecteur ou de travailler sur la charge.

PRECAUCIÓN

Desconecte la alimentación del freno de circuito

antes de instalar el sensor o de trabajar en la carga.

SPECIfICATIONS

Voltages:

WSP101 & WSP201 ......................... 120/277VAC, 50/60Hz
Load Limits for each relay:

@120VAC .....................0-800W tungsten or ballast, 1/6 HP
@277VAC ...................................................0-1200W ballast
Load Type Compatibility:

Incandescent, fluorescent, magnetic or electronic ballast
Horsepower Rating (each relay) .............. 1/6 HP @120VAC
Time Delay Adjustment .................................... 5 to 30 minutes

Walk-Through Mode .....3 minutes if no activity after 30 sec.
Test Mode ........... 5 sec. for 10 min. with DIP switch setting
PIR Adjustment ................................. High or Low (DIP switch)
Light Level Adjustment ........................................ 8fc to 180+fc
Alerts ............................................ Selectable Audible & Visual

SPÉCIfICATIONS

Tensions :

WSP101 & WSP201 ......................... 120/277 V c.a., 50/60 Hz
Limites de charge pour chaque relais :

@120 V c.a. .............. 0-800 W tungstène ou ballast, 1/6 HP
@277 V c.a. ...............................................0-1200 W Ballast
Compatibilité du type de charge :

ballast incandescent, fluorescent, magnétique ou

électronique

Puissance nominale

(pour chaque relais) .............................. 1/6 HP @120 V c.a.

Réglage de la temporisation ............................. 5 à 30 minutes
Mode Passage ............................3 minutes s’il n’y a aucune

activité après 30 secondes

Mode Test ..................................... 5 sec. pour 10 min. avec

réglage d’interrupteur DIP

Réglage PIR .........................Élevé ou faible (interrupteur DIP)
Réglage du niveau de luminosité ..................De 8 fc à 180 +fc
Alarmes ...................................Sonore et/ou visuelle, au choix

ESPECIfICACIONES

Voltajes:

WSP101 y WSP201 ........................ 120/277 VAC, 50/60 Hz
Límites de carga para cada relé:

a 120 VAC ............ Tungsteno o balasto de 0-800 W, 1/6 HP
a 277 VAC ........................................... Balasto de 0-1200 W
Compatibilidad de tipo de carga:

Balasto incandescente, fluorescente, magnético o electrónico
Especificaciones de caballo

de fuerza (cada relé) ................................1/6 HP a 120 VAC
Ajuste del tiempo de retardo........................De 5 a 30 minutos

Modo de Recorrido ................................3 minutos si no hay

actividad después de 30 segundos

Modo de Prueba ........ 5 seg. por 10 min. con configuración

del conmutador selector para bascular

Ajuste PIR........................................Alto o bajo (interruptor del

conmutador selector para bascular)

Ajuste de nivel de luz............................................ 8fc a 180+fc
Alertas ......................................Seleccionable audible y visual

4’

(1.2m)

20’

(6.1m)

35’

(10.6m)

0

Side View

UNIT DESCRIPTION AND OPERATION

The WSP Passive Infrared Wall Switch sensors use advanced passive infrared (PIR) technology.
The WSP sensor can turn a load on, and hold it on as long as the sensor detects occupancy. After no movement

is detected for the selected time delay, the lights switch off. A “walk-through” mode can turn lights off after only 3

minutes, if no activity is detected after 30 seconds following an occupancy detection.
The WSP101 has one relay and one

ON/Off button. The WSP201 contains two relays and two ON/Off buttons to

allow control of one or two loads independently. Pressing a button toggles the state of the corresponding relay.
WSP sensors contain a light level sensor. If adequate daylight is present, the sensor holds the load

Off until light

levels drop, even if the area is occupied. In the WSP201, light level only affects the load on Relay 2. Users can

overrule the hold

Off function by pressing the ON/Off button. See Light Level Adjustment.

Turning Load(s) ON (ON Mode)

The relays are programmed independently for either Auto

ON or Manual ON. In either mode, the load can be turned

ON or Off using the ON/Off button.

Manual ON

DIP 8 ON for Relay 1

DIP 9** ON for Relay 2

With an

ON Mode DIP switch in the ON position, the occupant must press the ON/Off

button to turn

ON the load. The sensor keeps the load ON until no motion is detected for

the selected time delay. There is a 30 second re-retrigger delay. If occupancy is detected

during the delay, the sensor turns the load back

ON. After the re-trigger delay elapses the

ON/Off button must be pressed to turn ON the load.

Auto ON

DIP 8 OFF for Relay 1

DIP 9** OFF for Relay 2

With an

ON Mode DIP switch in the Off position, the load turns ON and Off

automatically based on occupancy. If the load is turned

Off manually, Presentation

Mode operation applies. This prevents the load from turning

ON automatically after it was

deliberately turned

Off. Pressing the button to turn lights ON returns the sensor to Auto

ON mode.

** WSP101: Switch 9 is not used. WSP201: Switch 9 default is

ON to comply with CA Energy Commission Title 24 bi-level switching

requirements.

Model #

Relay

Default ON Mode

DIP switch #

Setting

WSP101

1

Manual ON

8

ON

WSP201

1

2

Auto ON

Manual ON

8

9

OFF

ON

Shading indicates default operation and switch setting.

Presentation Mode is a feature of the Auto ON mode. When both relays are manually turned Off the WSP holds

the lights

Off until no motion has been detected for the duration of the Time Delay. With subsequent occupancy,

the WSP turns the load

ON. If both relays are ON and one relay is manually turned Off this relay remains Off

until both the Time Delay and retrigger delay expires for the relay that is

ON, after that time the ON Mode control

settings again apply.

Time Delays

The WSP sensor holds the load

ON until no motion is detected for the selected time delay. Select the time delay

using DIP switch settings. In the WSP201, both relays use the same delay.

Test/20 min

(DIP 1, 2, 3,

Off)

A Test Mode with a short time delay of 5 seconds is set when DIP switches 1, 2, & 3

are

Off. It cancels automatically after ten minutes, or when you set a fixed time delay.

When the Test Mode times out, the sensor assumes a 20 minute time delay. To restart

Test Mode, change the time delay setting to any fixed amount and then return it to the

Test setting.

fixed Time Delay

(DIP 1 ON, 2 & 3 OFF)

Time delays are 5, 10, 15,

20 (default), 25, or 30 minutes.

Walk-Through

The Walk-Through mode shortens the time delay to reduce the amount of time the load is

ON after a brief moment

of occupancy, such as returning to an office to pick up a forgotten item then immediately exiting.

Walk-Through Mode

(DIP #4 ON)

The WSP sensor turns the load

Off three minutes after the area is initially occupied, if

no motion is detected after the first 30 seconds. If motion continues beyond the first 30

seconds, the set time delay applies.

No Walk-Through

DIP #4 OFF)

Walk-Through mode disabled.

PIR Sensitivity Adjustment

The WSP sensor constantly monitors the controlled environment and automatically adjusts the PIR to avoid

common ambient conditions that can cause false detections, while providing maximum coverage.

Walk-Through Mode

(DIP #4 ON)

Default setting. Suitable for most applications.

Low, 50%

(DIP #5

ON)

Reduces sensitivity by approximately 50%. Useful in cases where the PIR is detecting

movement outside of the desired area (also consider masking the lens) and where heat

sources cause unnecessary activation.

Alerts

The WSP can provide audible and/or visible alerts as a warning before the load turns OFF.

Visible Alert

(DIP #6

ON)

When only one minute is left in the time delay, the load connected to the relay turns

Off for one second. This provides a one minute warning before the load(s) are turned

Off by the sensor.

No Visible Alerts

(DIP #6

Off)

No visible warnings provided.

Audible Alerts

(DIP #7

ON)

Unit will beep at one minute*, at 30 seconds and at 10 seconds before turning

Off

load. When Walk-Through is active, the unit beeps three times at 10 seconds before the

load goes

Off.

* If Visible Alert is also

ON, the one-minute time-out warning beep is replaced by the

visible alert.

No Audible Alerts

(DIP #7

Off)

No audible warnings provided.

COVERAgE PATTERNS

Coverage testing has been performed according to the NEMA

WD 7 guideline. For best performance, use in spaces not larger

than 15' x 12'.

PIR Sensor

The sensor has a two-tiered, multi-cell viewing Fresnel lens with

180 degree field of view. The red LED on the sensor flashes when

the PIR detects motion.

Masking the lens

Opaque adhesive tape is supplied so that sections of the PIR

sensor’s view can be masked. This allows you to eliminate

coverage in unwanted areas. Since masking removes bands of

coverage, remember to take this into account when troubleshooting

coverage problems.

INSTALLATION

WARNINg

Turn the power off at the circuit breaker before installing the sensor

or working on the load.

1. Make sure that the power has been turned

Off at the circuit breaker.

2. Connect wires to the WSP flying leads as shown in the wiring diagram that is

appropriate to the WSP model and electrical supply.

The 2 ground wires (green

and green/yellow) must be fastened to ground for the sensor to work properly.

3. Attach the sensor to the wall box by inserting screws into the two wide holes on the

top and bottom of the attached metal bracket. Match them up with the holes in the wall box and tighten.

4. Turn the circuit breaker

ON. Wait one minute, then push the Auto ON/Off switch for each load and the lights will

turn

ON. There is a delay due to initial power-up of the sensor that only occurs during installation.

5. Test and adjust the sensor if necessary.
6. Install industry standard decorator wall switch cover plate (not included).

WSP201 Bi-Level Wiring

Neutral

Blue

Line

Black

Secondary

Load

Brown

Primary

Load

Red

Ground

Green

Neutral White

Azul

Carga

principal

Carga

secundaria

Neutro

Rojo

Marrón

Línea 2

Línea 1

Neutro

Tierra

Verde

Negro

Neutro

Blanco

WSP201 Dual Circuit Wiring

Load

Red

Neutral White

Neutral

Ground

Green

Line Black

WSP101 Wiring

DIP SWITCh SETTINgS

DELA

Y

PIR 50%

WA

LK

AUD. ALERT

RL

Y 1 MAN

RL

Y 2 MAN

VIS. ALERT

DIP Switches

ON/Off Buttons

Relay 1

Relay 2

PIR Lens

Detection

LED

Button

hinges

Tabs

WSP201 shown.

WSP101 has a single button.

WSP101

WSP201

PIR

Coverage

7.5’

(2.2m)

15’

(4.5m)

20’

(6.1m)

35’

(10.6m)

Major motion

Minor motion

Top View

This manual is related to the following products: