Legrand S4000 Stainless Large Raceway Raceway User Manual
Installation instructions, S4000 stainless steel raceway, S4000 raceway wire fill capacities for power
TELEPHONE CABLE-TYPE CM/CMR 24 AWG
COAXIAL
IBM CABLING
NUMBER OF PAIRS
RG62A/U
RG6/U
RG59/U
RG58A/U
SYSTEM
SIGNAL WIRE
CABLE TYPE
100
75
50
25
6
4
3
2
22 Gage
18 Gage 20 Gage
20 Gage
Type 1 Type 2 18AWG 20 AWG 22 AWG 24 AWG
Nominal O.D. Inches
0.68
0.60
0.50
0.38
0.22
0.18 0.14
0.12
0.26
0.275
0.242
0.195
0.43
0.51
0.066
0.057
0.05
0.044
Capacity @ 30% XSA
6
8
11
20
59
88
146
199
42
38
49
75
16
11
658
882
1146
1480
Capacity of Divided
@ 30% XSA
3
4
6
10
29
44
72
98
21
19
24
37
8
5
325
435
566
730
Capacity @ 60% XSA
12
16
23
40
118
177
292
398
85
76
98
151
31
22
1316
1764
2293
2961
Capacity of Divided
@ 60% XSA
6
8
11
20
58
87
144
196
42
37
48
74
15
11
649
870
1131
1461
Installation
Instructions
S4000 Raceway Wire Fill Capacities for Power
POWER WIRING
WITHOUT DEVICES
WITH DEVICES
Wire Size (AWG)
Non-Divided
Divided
Non-Divided
Divided
(THHN/THWN)
O.D.
40% Fill
40% Fill
40% Fill
40% Fill
2
0.388
25
13
12
5
4
0.328
35
18
16
7
6
0.257
58
29
26
11
8
0.218
80
40
37
15
10
0.153
163
81
74
30
12
0.122
257
127
117
48
14
0.105
347
171
158
64
S4000 Data/Communication Wire Fill Capacities
NOTES: 1) XSA = Cross Sectional Area of S4000 Surface Raceway.
2) Capacity range is calculated at 30% to 60% of raceway area as stated in the Commercial Building Standard for
Telecommunications Pathways and Spaces, EIA/TIA-569.
3) Reduce wirefill by 20% when fittings are to be used in installation.
All Wiremold electrical products, unless specifically noted, are listed by Underwriters’ Laboratories, Inc. and conform to U.S.
Federal Specification W-C-582. They comply with the National Electrical Code. Products designed primarily for use in tele-
phone or communications wiring and tools normally do not require U.L. Listing or CSA certification. Most products are CSA
certified in compliance with the Canadian Electrical Code. All products must be installed in a manner consistent with applic-
able electrical codes. Wiremold S4000 Stainless Steel Surface Raceway is CSA certified (File No. LR350) and listed by
Underwriters’ Laboratories (File Nos. E4376 [Raceway] and E41751 [Fittings]). This product is in compliance with the
National Electrical Code and the Canadian Electrical Code.
See typical basic system (illustrated on back) for installation details. In general, the following procedure for installing S4000
is recommended.
1.
Starting at feed connection, install S4000 Base sections over entire run. Butt ends of sections and install couplings as
shown on back of this sheet. Cut base sections to length as required for connection of bases of fittings. Custom pre-
cut base and cover lengths are available and recommended to ensure an expeditious installation.
2.
Assemble device brackets in S4000 Base.
3.
Install wiring in base and wire devices.
4.
Assemble devices and device covers in S4000 Base.
5.
Cut S4000 Cover sections to length as necessary and snap onto base. It is recommended that covers overlap base
joint.
6.
Tighten all fitting locking screws securely.
S4000 Stainless Steel Raceway
NOTES: 1) % Fill is based on use of Surge/GFCI style devices, mounted perpendicular in raceway.
2) Reduce wirefill by 20% when fittings are to be used in installation.