CABLE/WIRE SIZE

O.D.

4015DFO

Inches

[mm]

40% Fill

POWER WIRING

2 Awg

0.388

[9.86]

6

THHN/THWN

4 Awg

0.328

[8.33]

9

6 Awg

0.257

[6.53]

14

8 Awg

0.218

[5.54]

20

10 Awg

0.153

[3.89]

40

12 Awg

0.122

[3.10]

63

14 Awg

0.105

[2.67]

85

UNSHIELDED

Cat. 5 UTP

0.220

[5.59]

19

TWISTED PAIR

Cat. 3 UTP

0.190

[4.83]

26

2 Pair

0.140

[3.56]

28

Telephone

3 Pair

0.150

[3.81]

42

4 Pair

0.190

[4.83]

26

25 Pair

0.410

[10.41]

6

RG58/U

0.195

[4.95]

25

COAXIAL

RG59/U

0.242

[6.15]

16

RG60/U

0.242

[6.15]

16

RG6/U

0.270

[6.86]

13

TWINAXIAL

100 Ohm

0.330

[8.38]

9

SHIELDED

Type 1 STP

0.390

[9.91]

6

TWISTED PAIR

Type 2 STP

0.465

[11.81]

4

Type 3 STP

0.245

[6.22]

16

FIBER OPTIC

Fiber ZipCord

0.110

[2.79]

78

Round Fiber 2 Strand

0.180

[4.57]

29

Round Fiber 4 Strand

0.190

[4.83]

26

Round Fiber 6 Strand

0.210

[5.33]

21

4011FO

4015FO / 4015DFO

Use #8 (5/16" [7.9mm] head size) flat head fasteners or equivalent to mount base to surface.

RACEWAY WIRE AND FILL CAPACITY WHEN USING 4015DFO

4011FO/4015FO/4015DFO/
4017FO/4018FO

I N S TA L L AT I O N I N S T R U C T I O N S

Installation Instruction No.: 41398R1 – Updated July 2004

This manual is related to the following products: