X-Unit:
(Field Installation of the standard three-compartment tunnels,
bridges, and partitions.)
Installation of Tunnels and Bridges:
1. Position the tunnels in the X-unit as shown.
2. Using the holes in the tunnel flange
as a guide, drill 5/32" holes through
the bottom of the X-unit.
3. Mount the tunnels with the #10-16
x 1/4" long screws provided.
NOTE: The tunnels and bridges may be welded in place.
4. Position the bridges in the X-unit as shown.
5. Refer to steps 2 and 3 to secure the bridges.
Installation of Partitions:
1. If the partitions of the adjoining
Wallduct sections have not
been installed when the X-unit
tunnels/bridges are assembled,
cut the partitions long enough to
abut the tunnels/bridges of the X-unit.
WARNING: Gaps between partitions, tunnels, or
bridges must not exceed 1/8" [3.2mm].
2. If the partitions of the adjoining Wallduct
sections have been installed prior to the
assembly of the X-unit tunnels/bridges,
cut partition pieces from excess straight
partitions as shown on the drawing.
These pieces are required to fit between
the straight body partitions and the
tunnels/bridges of the X-unit.
X-Unit – All Components Field Installed.
Bridge
Tunnel
Partitions
Partitions
Partitions