Legrand ALDS4000 Designer Series Large Raceway Activation User Manual
Page 3
CABLE
CATEGORY/
O.D.
40% FILL 1/2
TYPE
DESIGNATION
Inches
[mm]
COMPARTMENT
UNSHIELDED
4-pair, 24 AWG Cat 3
0.190
[4.8]
68
TWISTED PAIR
4-pair, 24 AWG Cat 5e
0.210
[5.3]
56
4-pair, 24 AWG Cat 6
0.250
[6.3]
40
4-pair, 24 AWG Cat 6a*
0.335
[8.5]
22
25-pair, 24 AWG
0.360
[9.1]
18
COAXIAL
RG6/U
0.270
[6.9]
34
FIBER
ZipCord
0.118 x 0.236
[3 x 6]
70
Round 4 Strand Fiber
0.187
[4.8]
71
Round 6 Strand Fiber
0.256
[6.5]
38
* Category 6 Augmented cable for 10 gigabit ethernet – max allowed cable diameter per Addendum 11 to
ANSI/TIA-568-B.2.
ALDS4000 Raceway Wire Fill Capacities for Communication
WIRE SIZE
O.D.
ALDS4011
ALDS4015
ALDS4017
ALDS4018
THHN
Inches
[mm]
40%
60%
40%** 60%**
40%**
60%**
40%**
60%**
THHN
14
0.111
[2.8]
122
182
49
73
75
112
133
199
12
0.130
[3.3]
89
133
35
53
54
82
97
145
10
0.164
[4.2]
56
84
22
34
34
51
61
92
8
0.216
[5.5]
32
48
13
19
20
30
35
53
6
0.254
[6.5]
23
35
9
14
14
21
25
38
UTP
2-pair, 24 AWG
0.150
[4.8]
67
100
27
40
41
61
73
109
4-pair, 24 AWG Cat 3
0.190
[4.8]
42
62
17
25
25
38
45
68
4-pair, 24 AWG Cat 5e
0.210
[5.3]
34
51
14
20
21
31
37
56
4-pair, 24 AWG Cat 6
0.250
[6.3]
24
36
10
14
15
22
26
39
4-pair, 24 AWG Cat 6a*
0.354
[9.0]
13
20
5
8
8
12
15
22
25-pair, 24 AWG
0.410
[10.4]
12
17
5
7
7
11
13
10
Coaxial RG6/U
0.270
[6.9]
21
31
8
12
13
19
22
24
Fiber
ZipCord
0.118 x 0.236 [3 x 6]
42
64
17
25
26
39
46
69
Round 4 Strand Fiber
0.187
[4.8]
43
64
17
26
26
40
47
70
Round 6 Strand Fiber
0.256
[6.5]
23
34
9
14
14
21
25
38
* Entrance end fitting fill rate is calculated using backfeed capability and radius inserts. Inserts are removable and fitting can
obtain maximum raceway fill from utilizing end fitting knockouts and removing radius control inserts.
**Calculated using radius control inserts. Inserts are factory installed and may be removed in order to obtain full raceway
capacity if radius control is not required.
ALDS4000 Raceway Fittings Wire Fill Capacity Chart
NOTE: For additional information, refer to the Technical Section of the current version of ED439 (Wiremold Buyer’s Guide).
NUMBER OF CONDUCTORS (40% FILL)
WIRE SIZE
O.D.
w/DUPLEX
w/SURGE
LARGE SINGLE
THHN/THWN
Inches
[mm]
WITHOUT
RECT. DEVICE
GFCI DEVICE
RECEPTACLE
DEVICES
1.59in.
2
[1025mm
2
]
2.30in.
2
[1485mm
2
]
3.00in.
2
[1935mm
2
]
14 AWG
0.111
[2.8]
200
134
105
76
12 AWG
0.130
[3.3]
146
98
77
56
10 AWG
0.164
[4.2]
92
62
48
35
8 AWG
0.216
[5.5]
53
36
28
20
6 AWG
0.254
[6.5]
38
26
20
15
ALDS4000 Raceway Wire Fill Capacities for Power