I N S T A L L A T I O N I N S T R U C T I O N S

Installation Instruction No.: IB0001 R1 – Updated February 2007

Wiremold / Legrand electrical systems conform to and should be
properly grounded in compliance with requirements of the current
National Electrical Code or codes administered by local authorities.

All electrical products may present a possible shock or fire
hazard if improperly installed or used. Wiremold / Legrand electrical
products may bear the mark as UL Listed and/or Classified and should
be installed in conformance with current local and/or the National
Electrical Code.

IMPORTANT: Please read all instructions

before beginning.

Products Covered: 437, 439

NOTE: Source I Fittings will run lengthwise on duct when

insert tabs are oriented toward the center as called
for in these instructions (see Figure 1).

AS A PRESET INSERT (437):

1. Install attaching ring in 2 1/2" [64mm] hole in raceway

before concrete is poured (see Figure A).

2. Hole can be factory prepunched or field drilled. Attaching

ring is secured by tightening locking tabs. Be sure the
locking tabs are oriented toward the center of the raceway
(see Figure B).

3. It is important that tabs on the attaching ring be properly

oriented on the duct so that activations will be aligned in
the desired direction. The mudcap should be securely in
place before the concrete pour. After the pour, chip away
concrete (see Figure C) and remove mudcap.

4. Go to Activation Instructions.

AS AN AFTERSET INSERT (437 or 439):

1. Establish location for the fitting, then core drill a 4" [102mm]

diameter hole in concrete (see Figure A). Do not drill
through the raceway
.

2. Drill a 2 1/2" [64mm] diameter hole through the top of the

raceway (see Figure B). It should be located in the center of
the core drilled hole.

3. Install attaching ring on raceway making sure the locking

tabs are oriented toward the center of the raceway (see
Figure C). It is important that tabs on the attaching ring be
properly oriented so that activations will be aligned.

4. Go to Activation Instructions.

Figure 1

Figure A

Figure B

Figure C

Attaching Ring

2 1/2" [64mm]
Hole

Walkerduct

Attaching Ring

Duct Direction

Locking
Tabs

Mudcap

Figure A

Figure B

Figure C

4" [102mm]
Hole

2 1/2" [64mm]
Hole

Duct

Attaching Ring

Duct Direction

Locking
Tabs

Tabs Outward

Duct Direction