Legrand WC Cellular Raceway Systems User Manual
Walkercell, Systems, General
General:
Review and become familiar with all Walkercell components. Be careful of sharp edges or burrs when
handling any sheet metal parts. All interior surfaces that can be touched by a wire shall be smooth.
Compare and coordinate the architectural and electrical drawings with the Wiremold installation drawings.
Contact your local Wiremold field sales representative immediately if any dimensions or details are incorrect.
Install Walkercell and related components in accordance with Article 356 of the latest issue of the National
Electrical Code. Keep material and cartons dry. Advise all trades that Walkercell is not to be used as a walkway
or crosswalk.
Provide a vapor barrier when duct is installed directly on grade. This barrier prevents ground moisture from
reaching the underside of the concrete slab through capillary action.
Laying Out the System:
Refer to the installation drawings to locate the position of the Headerducts and Junction Boxes. Strike a base line
to correspond with the center of all runs.
Use either bench marks on walls or columns or a laser type system to level the system.
The complete header systems (including risers) should be installed before installation of the Walkercell is begun.
Installing the Headerduct:
The Headerduct is furnished with a coupling strap that creates a male/female relationship. At the electrical or
communications room the Headerduct will have the male end exiting the room. Position the next piece of Headerduct
by sliding the female end of the piece to be positioned onto the male end of the Headerduct exiting the room. Using
the adjusting feet, secure the Headerduct to the form with nails, screws, or other suitable fasteners. Adjust to level.
Secure the coupling support across the top of the Headerduct with the screws provided.
IMPORTANT - PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING.
SAVE THESE INSTRUCTIONS FOR REFERENCE AND ADDITIONAL WORK REQUIRED
AFTER CONCRETE POUR.
Walkercell
®
Systems
I N S T A L L A T I O N I N S T R U C T I O N S
Installation Instruction No.: PDD-880R1 – Updated March 2010
Wiremold electrical systems conform to and should be properly
grounded in compliance with requirements of the current National
Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire
hazard if improperly installed or used. Wiremold electrical products
may bear the mark as UL Listed and/or Classified and should
be installed in conformance with current local and/or the National
Electrical Code.
IMPORTANT: Please read all instructions
before beginning.