24s plugmold, Recommended installation steps feed methods – Legrand 2400 Series Steel Plugmold Multioutlet System with Insulated/Isolated Grounding Receptacles User Manual
Page 2
Wiremold Electrical Systems conform to and should be installed and properly grounded in compliance with
requirements of the current National Electrical Code, Canadian Electrical Code or codes administered by local
authorities.
All electrical products may represent possible shock or fire hazard if improperly installed or used. Wiremold
electrical products are UL Listed, made for interior use only, and should be installed in conformance with current
local and/or the National Electrical Code.
Los Sistemas Eléctricos Wiremold cumplen con los requisitos del Código Nacional Eléctrico, el Código Canadiense
Eléctrico o los códigos vigentes administrados por autoridades locales, así mismo deben instalarse y conectarse a
tierra en la forma debida siguiendo los requisitos de los códigos antes mencionados.
Todos los productos eléctricos pueden provocar posibles choques o peligros de incendio si se instalan o usan de
manera indebida. Los productos eléctricos Wiremold están registrados bajo el cUL, se fabrican sólo para uso en
interiores y deben instalarse de acuerdo con el Código Nacional Eléctrico y cualquier otro código vigente.
Les Systèmes électriques Wiremold se conforment aux versions actuelles du Code national de l’électricité, du Code
canadien de l’électricité ou des règlementés par les autorités locales, et doivent être installés et correctement mis à
la terre les exigences du code approprié.
Tout produit électrique peut présenter un danger de choc électrique ou d’incendie s’il n’est pas installé ou utilisé
correctement. Les produits électriques de Wiremold sont répertoriés par les Laboratoires des Assureurs du
Canada (LAC), ne sont destinés qu’à l’usage intérieur et doivent être installés conformemént aux versions
actuelles des règlements locaux et/ou du Code national de l’électricité.
24S PLUGMOLD
®
RACEWAY & MULTIOUTLET SYSTEM
WITH INSULATED/ISOLATED
GROUNDING RECEPTACLES
I N S TA L L AT I O N I N S T R U C T I O N S
END FEEDING FROM FLEXIBLE OR RIGID METAL
CONDUIT (Using V2410A Entrance End Fitting)
2A W30 METHOD
2B WIRE NUT METHOD
Mount V2400 Base and Harness on surface with
#10 Panhead screws. Insert V2410A Entrance End
Fitting Base (available separately) into end of V2400B
Raceway Base. Assemble 1/2" connector (not supplied)
in V2410A and bring in-feed cable with wires
extending at least 2 1/2" [64mm] beyond connector.
Connect green grounding wire in harness to insulated
ground wire in-feed which is connected directly to
service grounding terminal. Connect black and white
harness wires to black and white feed wires with W30
Wire Connectors (available separately) inserting only
conductors of same color in a connector. See “W30
Wire Connectors… How to Use.” Do not use W30
Wire Connectors with ground wires. Any unused wire
leads must be individually closed up with a wire nut.
Do not connect unused leads together.
Snap V2410A Fitting Cover onto raceway base. Cut
raceway cover to fit and snap onto raceway base.
RECOMMENDED INSTALLATION STEPS
FEED METHODS
PARTS INCLUDED:
V2400B Base Section (1 ea.) with
insulated/isolated grounding type
receptacles rated 20A, 125V,
prewired with No. 12 type THHN
conductors and snapped into base
V2400C Cover Section (1 ea.)
2401
Coupling (1 ea.)
V2410B Blank End Fitting (2 ea.) (not shown)
1. Layout raceway path on mounting surface.
2. Locate power feed point, then install raceway base & harness (see
installation instructions that follow).
3. Wire according to instructions.
4. Install raceway covers. If any cuts are necessary, hold raceway cover
up against mounted raceway base/harness so that receptacle holecuts
match with receptacles. Mark cover and cut.
5. Install fitting covers last over raceway covers (excluding 2410A
Entrance End Cover).
NOTE: FOR EASE OF INSTALLATION AT CORNERS – Cut out any
receptacle within 4" [102mm} of wall corner. This will allow
sufficient space within raceway for wire connections where two
runs meet. Cut a blank raceway cover piece to fit over any
exposed area. if necessary.
Units may be end-fed as in Step 1A, through V2410A
Entrance End Fitting or back-fed as in Step 2A or 2B
through the 1/2" entrance knockouts in base.
V2410A Entrance
End Fitting
V2400B
V2410 Fitting Cover
2 1/2"
[64mm]
R
R
CAUTION: Conventional grounding
wire connection required for metal
raceway casing.
V2400B
NM2027, 20A, 125V
Receptacles Insulated/
Isolated grounding type
24S Wiring Harness
V2400C
W30 Wire Connectors*
Insulated conductor in-feed
which is connected directly to
service grounding terminal
V2400B
2409
Ground Clamp*
Green Wire – Ground
Separate Equipment
Ground (Required)
White Wire – Neutral
Black Wire – Hot
Black Wire – Hot
Wire Nuts*
V2400B
2409
Ground Clamp*
Jumper Wire(s)
Insulated Conductor In-Feed
Which Is Connected Directly to
Service Grounding terminal
Green Insulated/Isolated
Grounding Conductor
Separate Equipment
Ground (Required)
White Wire – Neutral
*Available separately
Black Wire – Hot
1A
2409 Ground Clamp*