Legrand 5B11N User Manual
Power commander, High current power distribution units
Wiremold / Legrand electrical systems conform to and should be
installed and properly grounded in compliance with the
requirements of the current National Electrical Code, Canadian
Electrical Code or codes administered by local authorities.
All electrical products may represent possible shock or fire hazard
if improperly installed or used. Wiremold / Legrand electrical
products should be installed in conformance with current local
and/or the National Electrical Code.
Power Commander
®
HIGH CURRENT
POWER DISTRIBUTION UNITS
I N S T A L L A T I O N I N S T R U C T I O N S
Installation Instruction No.: 1 007 920 – September 2008
The Wiremold Power Commander
®
Power Distribution Units are Listed by TUV Rheinland and meet UL60950-1.
MOUNTING INSTRUCTIONS
Locate and insert Screw for
bottom of the Unit Mount. Keep
Screw loose enough to be able
to slide in bottom of Unit
Mounting Ear.
Locate and insert Screw for top
of Unit Mount. Keep it loose.
Slide Unit bottom Mounting Ear
in first and swivel until top
Mounting Ear slides behind top
Mounting Screw. Tighten all
Screws
Wiremold / Legrand
U.S. and International:
60 Woodlawn Street • West Hartford, CT 06110
1-800-621-0049 • FAX 860-232-2062 • Outside U.S. 860-233-6251
Canada:
570 Applewood Crescent • Vaughan, Ontario L4K 4B4
1-800-723-5175 • FAX 905-738-9721
1 007 920 – September 2008 – For latest specs visit www.wiremold.com
© Copyright 2008 Wiremold / Legrand All Rights Reserved
CAUTION: All units are designed for interior use in dry
locations only. Check all local and national electrical codes
for proper installation.
ABOUT YOUR WIREMOLD PRODUCT: Each unit is 100%
tested prior to packaging. Power Commander
®
products are
specifically made for use in the IT environment.
TROUBLESHOOTING: If you are receiving no power to your
Wiremold product, first make sure the unit is plugged firmly
into your wall outlet. Plug the unit into a different wall outlet to
verify the condition. If there is still no power, the built-in circuit
breaker may need to be reset. If you are still having problems,
please call technical support.
OPERATING PARAMETERS:
Temperature: 10° –
40°C
Humidity:
30% – 70%
Altitude:
Below 2000 meters
MODELS
INPUT OUTPUT
5B11N, 5W11N
120V, single phase, 50/60 Hz, 50A, derated to 40A
Circuit 1 – 120V, 50/60 Hz, 20A
Circuits 2 & 3 – 120V, 50/60 Hz, 15A
6B21E, 6W21E
120/208V, three phase, 50/60 Hz, 30A, derated to 24A
Circuits 1, 2 & 3 – 120V, 50/60 Hz, 20A
6B21N, 6W21N
6B22E, 6W22E
120/208V, three phase, 50/60 Hz, 30A, derated to 24A
Circuits 1, 2 & 3 – 208V, 50/60 Hz, 20A
ELECTRICAL RATINGS