Legrand NP800 Series User Manual
Np800 series, Jumbo tele-power, Pole
NP800 Series
Jumbo Tele-Power
®
Pole
I N S TA L L AT I O N I N S T R U C T I O N S
Installation Instruction No.: INS00006R1 – Updated April 2005
Wiremold Electrical Systems conform to and should be
installed and properly grounded in compliance with
requirements of the current National Electrical Code, Canadian
Electrical Code or codes administered by local authorities.
All electrical products may represent possible shock or fire
hazard if improperly installed or used. Wiremold electrical
products are UL Listed to U.S. and Canadian safety
standards, made for interior use only, and should be installed
in conformance with current local and/or the National
Electrical Code.
NP800 Series Tele-Power Poles are provided standard with an anodized aluminum finish or may be painted any number of color
selected from a full array of powder coat finishes. Standard poles have two channels of different depths. These channels may be
divided at various locations by snap-in dividers to form additional channels. All channels may enclose either power or
communication wiring. Wire fill capacities are outlined below, followed by illustrations of standard pole hardware, and instructions
for a typical installation (over). Poles may be supplied with box ends of various sizes. Walkerflex™ Manufactured Wiring System
Connectors or with 10' [3.04m] cord ends (cUL only).
CABLE TYPE
UNSHIELDED TWISTED PAIR
SHIELDED TWISTED PAIR
COAX
TWINAX
DESCRIPTION
CAT 3
CAT3
CAT5e
CAT5
CAT6
TYPE 1
TYPE 2
TYPE 9
RG58/U
RG59/U
RG62
RG6U
100 OHM
4 PAIR
25 PAIR
4 PAIR
25 PAIR
4 PAIR
22 AWG
22 AWG
22 AWG
20 AWG
22 AWG
22 AWG
18 AWG
NOMINAL O.D. (In.)
0.19
0.36
0.21
0.337
0.25
0.39
0.465
0.275
0.195
0.242
0.242
0.27
0.24
2.4
25.0
7.0
20.0
8.0
14.0
6.0
4.0
12.0
24.0
15.0
15.0
12.0
15.0
2.8
29.0
8.0
24.0
9.0
17.0
7.0
4.0
14.0
28.0
18.0
18.0
14.0
18.0
3.2
33.0
9.0
27.0
10.0
19.0
8.0
5.0
16.0
32.0
20.0
20.0
16.0
21.0
4.2
44.0
12.0
36.0
14.0
25.0
10.0
7.0
21.0
42.0
27.0
27.0
22.0
27.0
4.3
45.0
12.0
37.0
14.0
26.0
10.0
7.0
21.0
43.0
28.0
28.0
22.0
28.0
4.8
50.0
14.0
41.0
16.0
29.0
12.0
8.0
24.0
48.0
31.0
31.0
25.0
31.0
5
52.0
14.0
43.0
16.0
30.0
12.0
8.0
25.0
50.0
32.0
32.0
26.0
33.0
5.2
55.0
15.0
45.0
17.0
31.0
13.0
9.0
26.0
52.0
33.0
33.0
27.0
34.0
5.8
61.0
17.0
50.0
19.0
35.0
14.0
10.0
29.0
58.0
37.0
37.0
30.0
38.0
6.2
65.0
18.0
53.0
20.0
37.0
15.0
10.0
31.0
62.0
40.0
40.0
32.0
41.0
7
74.0
20.0
60.0
23.0
42.0
17.0
12.0
35.0
70.0
45.0
45.0
36.0
46.0
7.7
81.0
22.0
66.0
25.0
47.0
19.0
13.0
38.0
77.0
50.0
50.0
40.0
51.0
8
84.0
23.0
69.0
26.0
48.0
20.0
14.0
40.0
80.0
52.0
52.0
41.0
52.0
12
126.0
35.0
103.0
40.0
73.0
30.0
21.0
60.0
120.0
78.0
78.0
62.0
79.0
DATA/COMMUNICATION: MAXIMUM WIRE FILLS FOR UL AND cUL LISTED TELE-POWER POLES
CAPACITY OF CROSS SECTION (In
2
)
SNAP-IN DIVIDERS AREAS OF CROSS SECTIONS
Large Compartment
Small Compartment
5"
[127mm]
2 13/16"
[71mm]
12 sq. in.
[7742mm
2
]
1 5/8"
[41mm]
4.3" sq. in.
[2774mm
2
]
7.7 sq. in.
[4698mm
2
]
2 3/16"
[71mm]
5.8" sq. in.
[3742mm
2
]
6.2 sq. in.
[4000mm
2
]
3 1/8"
[79mm]
5" sq. in.
[3226mm
2
]
7 sq. in.
[4516mm
2
]
1 5/8"
[41mm]
3.4" sq. in.
[2194mm
2
]
4.3 sq. in.
[2774mm
2
]
5"
[127mm]
1 15/16"
[49mm]
8 sq. in.
[5161mm
2
]
1 5/8"
[41mm]
2.8" sq. in.
[1806mm
2
]
5.2 sq. in.
[3355mm
2
]
2 3/16"
[71mm]
3.8" sq. in.
[2452mm
2
]
4.2 sq. in.
[2710mm
2
]
3 1/8"
[79mm]
3.2" sq. in.
[2065mm
2
]
4.8 sq. in.
[3097mm
2
]
1 5/8"
[41mm]
2.4" sq. in.
[1548mm
2
]
2.8 sq. in.
[1806mm
2
]
NOTE: Capacity range is calculated at 30% of raceway areas as stated in the Commercial Buildings Standard for Telecommunication Pathways
and Spaces, EIA/TIA-569.
These are the approximate diameter and cross-sectional areas for typical cables in each category. Check with the cable manufacturer for
more accurate dimensions.