beautypg.com

Legrand AMD8 Abandonment Plugs User Manual

Page 2

background image

The Wiremold Company
U.S. and International:
60 Woodlawn Street • West Hartford, CT 06110
1-800-621-0049 • FAX 860-232-2062 • Outside U.S.: 860-233-6251
Canada:
850 Gartshore Street • Fergus, Ontario N1M 2W8
1-800-741-7957 • FAX 519-843-5980

1 002 048 R3 0504

© Copyright 2004 The Wiremold Company All Rights Reserved

NOTE: These instructions cover abandoning all 3-inch and 4 inch core holes.

Step 1 Locate poke-thru unit or core hole that needs

to be sealed with an abandonment plug.

Step 2 Remove slide holder assembly and the internal gasket.

Disconnect power and communications devices and
remove flange.

Step 3 Remove poke-thru unit from hole.

Step 4 Push in proper abandonment plug.

For 3" core hole, use ABPLUG3
For 4" core hole, use ABPLUG4

Step 5 Installation complete.

NOTE: Abandonment Plugs are required to maintain the fire rating of the floor assembly when ever a poke-thru fitting is not used.

The abandonment plugs in these instructions are shown in the UL Fire Resistance Directory.

ABPLUG3 & ABPLUG4 INSTALLATION: