beautypg.com

Legrand AC User Manual

Ac raised floor box, Installation instructions, Step 1

background image

Products Covered: AC Series Floor Boxes, P Series Device Plates for Power, and C Series Device Plates for Communication.

NOTE: Products are suitable for use in air handling spaces in accordance with Sec. 300-22(C) of the National Electrical Code.

Step 1

Determine box location on panel and cut the following size hole:

Step 2

Field Wiring – Power: Pull 1/2" [12.7mm] or 3/4" [19.1mm]
trade size flexible conduit through raised floor panel and
attach to box with conduit fitting. Wire receptacles according
to NEC and local codes.

Step 4

Place device plate in box. Position bottom of plate
behind stops in floor of box. Roll plate into position
and mount with screws provided.

NOTE: Communication window cover required

only if box is all power wiring, or if using
conduit to supply communications cabling
(See Step 7).

Step 3

Remove screw from receptacle mounting strap.
Reinsert screw through the power device plate
and receptacle strap and attach with #6-32
hex nut.

AC Box Model

Use Power Device Plate Series

AC8840

P8840-(suffix)

AC8850

P8850-(suffix)

AC8104

P8104-(suffix)

AC8104-90-MS

Consult Factory

AC8105

P8105-(suffix)

AC10105-2

P10105-(suffix)

AC10105-2-AT

P10105-(suffix)

AC10105-2-90-UB

P10105-(suffix)

Bottom Stop

Communication
Window Cover

AC Raised Floor Box

INSTALLATION INSTRUCTIONS

Installation Instruction No.: IJ0175 R4 – Updated November 2006

Wiremold / Legrand electrical systems conform to and should be
properly grounded in compliance with requirements of the current
National Electrical Code or codes administered by local authorities.

All electrical products may present a possible shock or fire
hazard if improperly installed or used. Wiremold / Legrand electrical
products may bear the mark as UL Listed and/or Classified and should
be installed in conformance with current local and/or the National
Electrical Code.

IMPORTANT: Please read all instructions

before beginning.

AC Box Model

Panel Cutout Dimensions

AC8840

8" x 8"

[203mm x 203mm]

AC8850

8" x 8"

[203mm x 203mm]

AC8104

8" x 10"

[203mm x 254mm]

AC8104-90-MS

8" x 10"

[203mm x 254mm]

AC8105

8" x 10"

[203mm x 254mm]

AC10105-2

10" x 10"

[254mm x 254mm]

AC10105-2-AT

10 1/8" x 10 1/8" [257mm x 257mm]

AC10105-2-90-UB

10" x 10"

[254mm x 254mm]