Legrand EFBFF User Manual
Page 3
1. Position box in accordance with job site floor plan and/or
engineering blue print. Use the dimensions give in the
following table as a reference for positioning.
WOOD OR RAISED FLOOR INSTALLATION (EFBFF):
WIDTH
LENGTH
BOX HEIGHT
5 15/16" [151mm]
7 1/4" [184mm]
4" [101.6mm]
2. Remove protective cover from box and drop box into
hole cut in floor.
3. At front and back sides of box are adjustable toggle
clamps that are used to secure box to floor. Clamps are
positioned to allow for up to 1-1/2" [38mm] thick floors.
Tighten clamps so that box is held securely to floor.
4. Remove required KOs from box and attach cable
fittings (not included), to box.
5. Attach cables as specified.
6. Reattach protective cover until ready to install
finish cover.
NOTE: Make sure that each compartment is properly
grounded in accordance with the National Electrical
Code and any local code that may apply.
BOX DIMENSIONS
Minimum: 7 1/4" [184mm]
Maximum: 7 7/16" [189mm]
Minimum: 6" [152mm]
Maximum: 6 1/8" [156mm]