Installing service heads and faceplates – Legrand FIT Fire-Rated Poke-Thru Devices User Manual
Page 2
2
Step 5. Orientation of receptacle shell.
Step 6. Conduit connection.
Step 7. Cut carpet to allow
for service fitting.
Use template on last page to
cut carpet for stem installation.
Tile Applications: Using a 2" [51mm]
diameter hole saw, drill an opening
concentric with the hole previously
IMPORTANT: Orientation of receptacle shell
After installation, place the sleeve into the
drilled into the tile.
critical during initial alignment.
two tabs and rotate down. Replace screws
Make sure to orient the power
to tighten sleeve.
side of poke-thru device facing
wires to be installed. Poke-thru
device cannot be rotated
after insertion into hole.
Installing Service Heads
and Faceplates:
Step 1. Remove screws and
Step 2. Connect base to poke-
Step 3. Connect communications
disposable cover.
thru device.
inserts and outlets.
NOTE: If base contains either all power
or all communications, the divider
plate may be removed. Otherwise,
the divider must remain in place.
Attach base to poke-thru stem as
shown. Make sure gasket seats
to floor when tightening.
Bases sold separately.
Push Down
Disposable Cover
(To Be Removed
at a Later Time)
Flooring
Tile or Carpet
200 Series
Divider Plate
241 Series
- AP-FITTC Fire-Rated Poke-Thru Devices FIT-EXT 241-H/BTC FP75-75 FIFP50 FIFP-SS FP2R FP75-50 FIFP-T FIFP-R FP1.390-1.390 FPB-2RT FP1.562-1.562 FIFP-B FPB-B FPSS-SS FIFP-1.562 FIFP-1.390 FP2T FPACT-ACT FPB-ACT FIFP75 FPB-RT FP50-50 200-H/BTC 221-21CARPET FIT Fire-Rated Poke-Thru Devices 221-21TILE FIT Fire-Rated Poke-Thru Devices