12. Double-check all connections.

13. Reattach cover to unit in appropriate direction, so that Sentrex logo reads straight across the unit.

14. The SPD can now be activated by turning on the circuit breaker. The green indicator lights will illuminate assuming the

unit has been installed properly.

SPD

120/240 VOLT SINGLE PHASE

120/240 Volt 1Ø 3W

Primary

Voltage

Secondary Voltage

120 Volts

240 Volts

Phase 1

Neutral

Phase 2

120T MODELS

Connect Line 1 from panel to Phase 1 on SPD.

Connect Line 2 from panel to Phase 2 on SPD.

NOTE: When using for 120V only and

connecting to only one phase,
connect Line 1 from panel to Phase 1
on SPD. Use the supplied jumper wire
to connect Phase 1 and Phase 2 on
the SPD.

DO NOT USE THE JUMPER WIRE IF
YOU ARE CONNECTING 240V.

Connect Ground (green wire) from panel to

Ground on SPD.

Connect Neutral (white wire) from panel to

Neutral on SPD.

120Y & 277Y MODELS

Lines from panel may be connected without

regard to Phase on SPD.

Ground (green wire) from panel to Ground

on SPD.

Neutral (white wire) from panel to Neutral

on SPD.

120 Volts

SPD

120/240 VOLT HIGH LEG DELTA

ØA

N

ØB

ØC

120 Volts

208 Volts +/-

High Leg

Phase 1

Neutral

Phase 3

Phase 2

120 Volts

240DCT MODELS

NOTE: Hi-Leg to Ground must be identified

and connected to Phase 2 ONLY.

USE EXTREME CAUTION WHILE MAKING
VOLTAGE MEASUREMENTS.

Ground (green wire) from panel to Ground on SPD.

Neutral (white wire) from panel to Neutral on SPD.

SPD

120/208 VOLT WYE

& 277/480 VOLT WYE

ØA

N

ØB

ØC

Phase 1

Neutral

Phase 3

Phase 2