beautypg.com

A52 inches, 0 inches, 36 inches – Greenheck ERCH (476054) User Manual

Page 8: Service clearances / access panel - heating only

background image

General Description - NOT model specific

Model ERCH Energy Recovery Ventilator

®

8

INDIRECT GAS FURNACE

ELECTRICAL BOX

EXHAUST FIL

TERS

OUTDOOR AIR

FIL

TERS

EXHAUST AIR

WEATHERHOOD

WHEEL CASSETTE

OUTDOOR

WEATHERHOOD

HEA

TING COIL

A

52 inches

CLEARANCE WITH

IG HEATER

0 inches

CLEARANCE WITHOUT

IG HEATER

ACCESS DOOR

B

ACCESS DOOR

*CASSETTE REMO

V

A

L

ACCESS DOOR

36 inches

ACCESS DOOR

PIPING VESTIBULE

(OPTIONAL)

ACCESS DOOR

*Cassette removal only available
on housing sizes 20 and 45.

Model

A (in.)

B (in.)

ERCH-20

48

36

ERCH-45

64

42

ERCH-55

42

42

ERCH-90

42

48

Service Clearances / Access Panel - Heating Only

Units require minimum clearances for access on all sides for routine maintenance. Filter replacement, drain pan
inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and belt adjustment are examples
of routine maintenance that must be performed. Blower and motor assemblies, energy recovery wheel cassette, coil
and filter sections are always provided with a service door or panel for proper component access.

Drawing shows both heating coil and indirect gas furnace options. Electric heat is also available. Only one can
be selected.