beautypg.com

Optional start-up components, Dirty filter switch, Economizer – Greenheck ERCH (476054) User Manual

Page 35

background image

General Description - NOT model specific

Model ERCH Energy Recovery Ventilator

®

35

Optional Start-Up Components

Dirty Filter Switch

To adjust the switch, the unit must be running with
all of the access doors in place, except for the
compartment where the switch is located (exhaust
intake compartment). The adjusting screw is located on
the top of the switch.

1. Open the filter compartment and place a sheet of

plastic or cardboard over 50% of the filter media.

2. Replace the filter compartment door.

3. Check to see if there is power at the alert signal

leads (refer to electrical diagram).

4. Whether there is power or not, turn the adjustment

screw on the dirty filter gauge (clockwise if you did
not have power, counterclockwise if you did have
power) until the power comes on or just before the
power goes off.

5. Open the filter compartment and remove the

obstructing material.

6. Replace the door and check to make sure that you

do not have power at the alert signal leads. The unit
is now ready for operation.

Economizer

Relevant Set Points

1. MAT SET The mixed air temperature set point after

the energy wheel. The control will modulate the
energy wheel to maintain temperature as best as it
can (Set point menu, default 53°F)

2. LOW T LOCK The set point for the low temperature

mechanical cooling lockout. (Set point menu, default
32°F)

3. DRYBLB SET The outdoor air set point to call for

economizer. (Set point menu, default 63°F)

4. MIN POS The minimum signal voltage sent to the

energy wheel. This must be set to 2 VDC. (Set point
menu, default 2.8 VDC)

5. AUX1 O The controllers operating sequence

structure. (Set point menu, default ‘None’)

6. ERV OAT SP The set point for low temperature

economizer lockout. This is the low temperature set
point when AUX1 O is set to ERV. (Set point menu,
default 32°F)

7. STG3 DLY Time delay after second cooling stage is

enabled (Advanced setup menu, default 2 hrs.)

Setscrew (on front of switch) must
be manually adjusted after the
system is in operation.

Negative pressure connection
is toward the ‘front or top’ of
the switch. (Senses pressure on
the blower side of filters)

Positive pressure connection is toward the ‘back or bottom’
of the switch. (Senses pressure at air inlet side of filters)

Using the Keypad with Settings and Parameters

To use the keypad when working with Set Points,
System and Advanced Settings, Checkout Tests, and
Alarms:
1. Navigate to the desired menu.

2. Press (enter) to display the first item in the

currently displayed menu.

3. Use the and buttons to scroll to the desired

parameter.

4. Press (enter) to display the value of the currently

displayed item.

5. Press the button to increase (change) the

displayed parameter value.a

6. Press the button to increase (change) the

displayed parameter value.a

7. Press (enter) to accept the displayed value and

store it in non-volatile RAM.

8. CHANGE STORED displays.

9. Press (enter) to return the current menu

parameter.

10. Press

(escape) to return to the current menu

parameter.

a When values are displayed, pressing and holding the

or button causes the display to automatically

increment.

The table shows which set points are relevant to the
given sequences. Refer to the wiring diagram for the
units’ sequence.

MODULATE WHEEL

STOP WHEEL

OA

Temp

OA

Enthalpy

OA/RA

Temp

Differential

OA

Temp

OA

Enthalpy

OA/RA

Temp

Differential

DRYBLB SET

X

X

MAT SET

X

X

X

X

X

X

LOW T LOCK

X

X

X

X

X

X

ERV OAT SP

X

X

X

MIN POS

X

X

X

AUX1 OUT

ERV

ERV

ERV

STG3 DLY

X

X

X

X

X

X

This manual is related to the following products: