General Description - NOT model specific

Model ERCH Energy Recovery Ventilator

®

40

Modulating Control for Fan Speed

(0-10 VDC)

Parameter

Setting

V1000

J1000

A1-01

Access Level

2

2

B1-17

VFD Start-Up Setting

1

1

C6-02

Carrier Frequency

1

1

D2-02

Ref Lower Limit

50%

50%

E2-01

Motor Rated FLA

Motor

FLA

Motor

FLA

H2-01

Terminal MA, MC Function

5

5

H3-04

Terminal A1 Bias

50%

50%

L4-01

H2-01 Frequency Detection

15

15

L5-01

Auto Restart Attempt

5

5

A1-01

Access Level

0

0

CO

2

Sensor Control for Fan Speed

(1/2 speed when CO

2

drops below 700 PPM)

(Full speed when CO

2

rises above 800 PPM)

Multi-Speed Control for Fan Speed

(1/3 or 1/2 speed reduction)

Parameter

Setting

V1000

J1000

A1-01

Access Level

2

2

B1-01

Reference Source (Frequency)

0

0

B1-17

VFD Start-Up Setting

1

1

C6-02

Carrier Frequency

1

1

D1-01

Frequency Reference 1

60 Hz

60 Hz

D1-02

Frequency Reference 2

40 Hz

40 Hz

D1-03

Frequency Reference 3

30 Hz

30 Hz

D1-04

Frequency Reference 4

60 Hz

60 Hz

D2-02

Ref Lower Limit

50%

50%

E2-01

Motor Rated FLA

Motor

FLA

Motor

FLA

H1-04

Multi-Function Input Sel 4

(Terminal S4)

3

3

H1-05

Multi-Function Input Sel 5

(Terminal S5)

4

4

H1-06

Multi-Function Input Sel 6

(Terminal S6)

5

NA

H2-01

Terminal MA, MC Function

5

5

H3-10

A2 Not Used

F

NA

L4-01

H2-01 Frequency Detection

15

15

L5-01

Auto Restart Attempt

5

5

A1-01

Access Level

0

0

Variable Frequency Drives for

Energy Recovery Wheel

Parameter

Setting – J1000

A1-01

Access Level

2

B1-17

VFD Auto Start

1

C1-04

Decel Time

600

*C4-01

Torque Gain

0.6

C6-02

Carrier Frequency

2

D2-01

Ref Upper Limit

40 or 50*

D2-02

Ref Lower Limit

5%

E2-01

Motor Rated FLA

Motor FLA

E2-03

Motor No-Load Current

Must be less

than FLA

H1-02

Multi-Function Input

(Terminal S2)

6

H2-01

Multi-Function Output

(MA, MB, MC)

4

H1-04

Multi-Function Input Sel 4

(Terminal S4)

7

Economizer Signal Source

(0-10 VDC)

Setting

Honeywell

Module

Carel

Controller

H3-03

Analog Frequency Reference

(Gain)

0

40 or

50*

H3-04

Analog Frequency Reference

(Bias)

40 or

50**

0

L1-01

Elect Thermal Overload

2

L2-01

Ride Thru Power Loss

2

L4-01

Frequency Detection Level

15

L5-01

Auto Restart Attempt

5

A1-01

Access Level

0

* 208/230 volt only
**36 through 52 inch wheels are 40 (24 Hz)
58 or 74 inch wheel is 50 (30 Hz)

CO

2

Proportional Control

Parameter

Setting

V1000

J1000

B1-17

VFD Start-Up Setting

1

1

C6-02

Carrier Frequency

1

1

D2-02

Ref Lower Limit

50%

50%

E2-01

Motor Rated FLA

FLA

FLA

H3-03

Analog Frequency Reference

(Gain)

150%

150%

H3-04

Analog Frequency Reference

(Bias)

25%

25%

L2-01

Ride Thru Power Loss

2

2

L4-05

Frequency Ref Loss

0

NA

L5-01

Auto Restart Attempt

5

5

A1-01

Access Level

0

0