General Description - NOT model specific

Model ERCH Energy Recovery Ventilator

®

50

Symptom

Possible Cause

Corrective Action

Compressor
short cycles

Thermostat location or controls malfunction.

Check thermostat, check heat anticipator setting.

Improper refrigerant charge.

Check subcooling, verify superheat.

Defective low pressure control.

Check high or low pressure switch.

Poor air distribution.

Check ductwork for recirculating.

High discharge pressure.

See “high discharge pressure”.

Low airflow at evaporator(s).

Check blower operation and airstream restrictions.

Incorrect unit selection (oversized).

Contact factory.

Compressor
loses oil

Refrigerant leak.

Check system for leaks. Repair leaks and add refrigerant.

Short cycling.

Check low pressure control settings.

Refrigerant flood back.

Check thermal expansion valve setting. Check for refrigerant
overcharge. Check crankcase heater operation.

Reheat flush cycle inadequate.

Contact factory.

Not enough
cooling or
lack of cooling

Refrigeration undercharged.

Check subcooling. Adjust charge, if necessary.

Dirty filter or evaporator coil.

Check filter, coil and airflow.

Dirty or clogged condenser coil.

Check coil and airflow.

Air or other non-condensables in system.

Check equalized high side pressure with equivalent outdoor
temperature.

Restriction in suction and liquid line.

Check for restrictions in refrigerant circuit.

Control contacts stuck.

Check wiring.

Excessive load.

Add more equipment or reduce room load.

Liquid line
is frosted
or wet

Restriction in liquid line.

Clear restriction upstream of point of frosting.

Suction line is
frosting

Insufficient evaporator airflow.

Check airflow, check filters, check VFD control signal for proper
operation.

Malfunctioning or defective expansion valve.

Check bulb of thermal expansion valve.

Frost on
evaporator
coil

Hot gas bypass valve not functioning
properly.

Check valve. If defective, replace.

Manual hot gas bypass valve closed.

Open valve.

Low load or airflow.

Increase airflow, check filters.

Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service
information.

Troubleshooting – Refrigeration Circuit

Troubleshooting - Energy Wheel

Symptom

Possible Cause

Corrective Action

Energy wheel
does NOT turn

Air seals are too tight.

See Air Seals in the Start-Up Components, Energy Wheel
section.

Broken belt.

Replace.

No power to wheel motor.

Make sure wheel drive is plugged in. Verify power is
available.

Energy wheel
runs intermittently

Wheel motor overloads are tripping due to
rubbing between wheel and air seals.

Recheck air seals, make sure they are not too tight. See
Adjust the Air Seals in the Start-Up Components, Energy
Wheel section.