beautypg.com

Greenheck ERCH (476054) User Manual

Page 22

background image

General Description - NOT model specific

Model ERCH Energy Recovery Ventilator

®

22

Auto Drain & Flush Valves

(when provided by Manufacturer)

Assembly

No.

Mfg

Part No.

ASCO

Part No.

Solenoid

Type

De-Energized

Position

Diameter Qty.

852178

461262

8210G2

Supply

Closed

1/2-inch

(12.7 mm)

1

461263 8262G262

Supply

Line

Drain

Open

1/4-inch

(6.35 mm)

1

461264 8210G35

Sump

Drain

Open

3/4-inch

(19.05 mm)

1

Part numbers subject to change.

Water Supply Connection Locations for Evaporative Cooler

EXHAUST FIL

TERS

OUTDOOR AIR FIL

TERS

WHEEL CASSETTE

ELECTRICAL BOX

INDIRECT

EVAP

DIRECT

EVAP

C

D

A

B

RETURN AIR

INTAKE

OUTDOOR AIR

INTAKE

Ø

0.875 Run 1/4 in. line up through 7/8 in. hole here and

bring around end of sump to supply connection.

1/4 in. water supply connection

1/4 in. water supply connection

Ø

0.875

Run 1/4 in. line up through 7/8 in. hole here

and bring around end of sump to supply connection.

Model

Water Supply Connection Locations

A

B

C

D

ERCH-20

37.5

4.5

4.5

46

ERCH-45

45.25

4.5

4.5

51.5

ERCH-55

56

4.5

4.5

57

ERCH-90

59

4.5

4.5

68

Dimensions from outside of unit (in inches)

This manual is related to the following products: