General Description - NOT model specific

Model ERCH Energy Recovery Ventilator

®

32

Frost Control Application / Operation Section:

Setting

Factory Default

Yes

No

Frost Control set point

5°F

Differential

2°F

Timer

Refer to IOM

Yes

No

Frost Control Modulating

Refer to IOM

Economizer Application / Operation Section:

Yes

No

Economizer (temperature)

Set point

65°F

Offset

20°F

Differential

2°F

Yes

No

Economizer (enthalpy)

Set point

B

Yes

No

Economizer (modulating)

Refer to IOM

Optional Accessories Section:

Operational

Yes

No

Wheel Rotation Sensor

(

1

8

in. from wheel)

Yes No N/A

Yes

No

OA Dirty Filter Sensor

Yes No N/A

Yes

No

EA Dirty Filter Sensor

Yes No N/A

Yes

No

CO2 Sensor

Yes No N/A

Yes

No

Service Outlet

Yes No N/A

Yes

No

Vapor Tight Lights

Yes No N/A

Yes

No

Remote Control Panel

Yes No N/A

Variable Frequency Drives Section:

Operational

Yes

No

Blower VFDs

Yes No N/A

Yes

No

Wheel VFD

Yes No N/A

Damper Section:

Operational

Yes

No

Outdoor Air Damper

Yes No N/A

Yes

No

Exhaust Air Damper

Yes No N/A

Yes

No

Night Setback Damper

Yes No N/A

Indirect Gas Furnace:

Yes

No

Refer to PVF/PVG Installation, Operation and Maintenance for start-up information.

Outdoor Air Monitoring:

Yes

No

Field calibrated.

Optional Accessories Checklist

Refer to the respective sections in this Installation, Operation and Maintenance Manual for detailed information.
Refer to wiring diagram in unit control center to determine what electrical accessories were provided.