General Description - NOT model specific

Model ERCH Energy Recovery Ventilator

®

20

Condensate Drain Trap

This unit is equipped with a stainless steel condensate
pan with a 1-inch MPT stainless steel drain connection.
It is important that the drain connection be fitted with a
P trap to ensure proper drainage of condensate while
maintaining internal static pressures.

A P trap assembly (kit) is
supplied with each unit and is
to be assembled and installed
as local conditions require and
according to the assembly
instructions provided with the
P trap. If local and area codes
permit, the condensate may
be drained back onto the roof,
but a drip pad should be provided beneath the outlet.
If local and area codes require a permanent drain line,
it should be fabricated and installed in accordance with
Best Practices and all codes.

In some climates, it will be necessary to provide freeze
protection for the P trap and drain line. The P trap
should be kept filled with water or glycol solution at
all times and it should be protected from freezing to
protect the P trap from damage. If severe weather
conditions occur, it may be necessary to fabricate a P
trap and drain line of metal and install a heat tape to
prevent freezing.

Pipe Size

(in. FPT)

Model

Tonnage

Number of

Connections

1

ERCH-20

4

2

ERCH-45

8

2

1.25

ERCH-20

5

2

ERCH-45

10

2

1.5

ERCH-20

6

2

ERCH-45

12.5

2

15

2

ERCH-55

15

2

2

ERCH-55

17.5

2

20

2

ERCH-90

20

2

25

2

30

2

Heat Pump Piping Sizes and Connections