Ductwork connections, Rail mounting / layout – Greenheck ERCH (476054) User Manual
Page 15

General Description - NOT model specific
Model ERCH Energy Recovery Ventilator
®
15
R
ot
atio
n
Length of Straight Duct
GOOD
Ductwork Connections
Examples of poor and good fan-to-duct connections
are shown. Airflow out of the fan should
be directed straight or curve the
same direction as the
fan wheel rotates. Poor
duct installation will result
in low airflow and other
system effects.
R
ot
atio
n
POOR
ERCH-20
Recommended Duct Size
Intake Duct Size Discharge
9-9 Blower
10-6 Blower
OIE
22 x 26
SDE
16 x 16
16 x 16
OIT
24 x 20
SDS
16 x 16
16 x 16
RIE
16 x 32
SDT
16 x 16
16 x 16
RIS
18 x 30
SDT/IG
28 x 24
28 x 24
RIB
16 x 32
SDB
12 x 14
12 x 14
RIT
16 x 32
EDE
16 x 16
16 x 16
EDT
16 x 16
16 x 16
EDS
16 x 16
16 x 16
ERCH-45
Recommended Duct Size
Intake Duct Size Discharge
12-8 Blower
12-12 Blower
9-9 Blower
OIE
28 x 36
SDE
20 x 20
16 x 16
OIT
34 x 24
SDS
20 x 20
16 x 16
RIE
24 x 40
SDT
20 x 20
16 x 16
RIS
26 x 32
SDT/IG
28 x 28
28 x 28
RIB
20 x 48
SDB
16 x 18
16 x 18
RIT
28 x 30
EDE
20 x 20
16 x 16
EDT
20 x 20
16 x 16
EDS
20 x 20
16 x 16
ERCH-55
Recommended Duct Size
Intake Duct Size Discharge 12-12 Blower 15-15 Blower
OIE
32 x 52
SDE
20 x 20
28 x 28
OIT
40 x 28
SDS
20 x 20
28 x 28
RIE
30 x 40
SDT
20 x 20
28 x 28
RIS
30 x 38
SDT/IG
38 x 30
38 x 30
RIB
20 x 54
SDB
16 x 18
18 x 20
RIT
30 x 40
EDE
20 x 20
28 x 28
EDT
20 x 20
28 x 28
EDS
20 x 20
28 x 28
ERCH-90
Recommended Duct Size
Intake Duct Size Discharge 15-15 Blower 18-18 Blower
OIE
34 x 64
SDE
28 x 28
32 x 32
OIT
34 x 50
SDS
28 x 28
32 x 32
RIE
32 x 60
SDT
28 x 28
32 x 32
RIS
40 x 40
SDT/IG
34 x 34
34 x 33
RIB
22 x 74
SDB
18 x 20
20 x 24
RIT
40 x 40
EDE
28 x 28
32 x 32
EDT
28 x 28
32 x 32
EDS
28 x 28
32 x 32
All dimensions shown in inches.
• Recommended duct sizes are based on velocities across the cfm
range of each model at approximately 800 feet per minute (FPM) at
minimum airflow and up to 1600 fpm at maximum airflow.
• Recommended duct sizes are only intended to be a guide and
may not satisfy the requirements of the project. Refer to plans for
appropriate job specific duct size and/or velocity limitations.
Inlet/Outlet Descriptions
Code Description
Code Description
OIE
Outdoor Air Intake End
SDT
Supply Discharge Top
OIT
Outdoor Air Intake Top
SDT/IG Supply Discharge Top w/IG
RIE
Return Air Intake End
SDS
Supply Discharge Side
RIS
Return Air Intake Side
SDB
Supply Discharge Bottom
RIB
Return Air Intake Bottom
EDE
Exhaust Discharge End
RIT
Return Air Intake Top
EDT
Exhaust Discharge Top
SDE
Supply Discharge End
EDS
Exhaust Out Side
Rail Mounting
Unit Size
A
B
ERCH-20
5.0
41.0
ERCH-45
7.0
41.9
ERCH-55
5.5
53.0
ERCH-90
6.0
59.0
All dimensions are in inches.
Rail Mounting / Layout
1. Rails designed to handle the weight of the unit
should be positioned as shown on the diagram (rails
by others).
2. Make sure that rail positioning does not interfere with
the supply air discharge opening or the exhaust air
intake opening on the unit. Avoid area dimensioned
“B” below.
3. Rails should run the width of the unit and extend
beyond the unit a minimum of 12 inches on each
side.
4. Set unit on rails.
B
A