beautypg.com

Ductwork connections, Rail mounting / layout – Greenheck ERCH (476054) User Manual

Page 15

background image

General Description - NOT model specific

Model ERCH Energy Recovery Ventilator

®

15

R

ot

atio

n

Length of Straight Duct

GOOD

Ductwork Connections

Examples of poor and good fan-to-duct connections
are shown. Airflow out of the fan should
be directed straight or curve the
same direction as the
fan wheel rotates. Poor
duct installation will result
in low airflow and other
system effects.

R

ot

atio

n

POOR

ERCH-20

Recommended Duct Size

Intake Duct Size Discharge

9-9 Blower

10-6 Blower

OIE

22 x 26

SDE

16 x 16

16 x 16

OIT

24 x 20

SDS

16 x 16

16 x 16

RIE

16 x 32

SDT

16 x 16

16 x 16

RIS

18 x 30

SDT/IG

28 x 24

28 x 24

RIB

16 x 32

SDB

12 x 14

12 x 14

RIT

16 x 32

EDE

16 x 16

16 x 16

EDT

16 x 16

16 x 16

EDS

16 x 16

16 x 16

ERCH-45

Recommended Duct Size

Intake Duct Size Discharge

12-8 Blower

12-12 Blower

9-9 Blower

OIE

28 x 36

SDE

20 x 20

16 x 16

OIT

34 x 24

SDS

20 x 20

16 x 16

RIE

24 x 40

SDT

20 x 20

16 x 16

RIS

26 x 32

SDT/IG

28 x 28

28 x 28

RIB

20 x 48

SDB

16 x 18

16 x 18

RIT

28 x 30

EDE

20 x 20

16 x 16

EDT

20 x 20

16 x 16

EDS

20 x 20

16 x 16

ERCH-55

Recommended Duct Size

Intake Duct Size Discharge 12-12 Blower 15-15 Blower

OIE

32 x 52

SDE

20 x 20

28 x 28

OIT

40 x 28

SDS

20 x 20

28 x 28

RIE

30 x 40

SDT

20 x 20

28 x 28

RIS

30 x 38

SDT/IG

38 x 30

38 x 30

RIB

20 x 54

SDB

16 x 18

18 x 20

RIT

30 x 40

EDE

20 x 20

28 x 28

EDT

20 x 20

28 x 28

EDS

20 x 20

28 x 28

ERCH-90

Recommended Duct Size

Intake Duct Size Discharge 15-15 Blower 18-18 Blower

OIE

34 x 64

SDE

28 x 28

32 x 32

OIT

34 x 50

SDS

28 x 28

32 x 32

RIE

32 x 60

SDT

28 x 28

32 x 32

RIS

40 x 40

SDT/IG

34 x 34

34 x 33

RIB

22 x 74

SDB

18 x 20

20 x 24

RIT

40 x 40

EDE

28 x 28

32 x 32

EDT

28 x 28

32 x 32

EDS

28 x 28

32 x 32

All dimensions shown in inches.

• Recommended duct sizes are based on velocities across the cfm

range of each model at approximately 800 feet per minute (FPM) at
minimum airflow and up to 1600 fpm at maximum airflow.

• Recommended duct sizes are only intended to be a guide and

may not satisfy the requirements of the project. Refer to plans for
appropriate job specific duct size and/or velocity limitations.

Inlet/Outlet Descriptions

Code Description

Code Description

OIE

Outdoor Air Intake End

SDT

Supply Discharge Top

OIT

Outdoor Air Intake Top

SDT/IG Supply Discharge Top w/IG

RIE

Return Air Intake End

SDS

Supply Discharge Side

RIS

Return Air Intake Side

SDB

Supply Discharge Bottom

RIB

Return Air Intake Bottom

EDE

Exhaust Discharge End

RIT

Return Air Intake Top

EDT

Exhaust Discharge Top

SDE

Supply Discharge End

EDS

Exhaust Out Side

Rail Mounting

Unit Size

A

B

ERCH-20

5.0

41.0

ERCH-45

7.0

41.9

ERCH-55

5.5

53.0

ERCH-90

6.0

59.0

All dimensions are in inches.

Rail Mounting / Layout

1. Rails designed to handle the weight of the unit

should be positioned as shown on the diagram (rails
by others).

2. Make sure that rail positioning does not interfere with

the supply air discharge opening or the exhaust air
intake opening on the unit. Avoid area dimensioned
“B” below.

3. Rails should run the width of the unit and extend

beyond the unit a minimum of 12 inches on each
side.

4. Set unit on rails.

B

A

This manual is related to the following products: