OUTDOOR UNIT

Refrigerant:

Default: R-22. Other selection: R410A.

Rated Amps

(Rated Amperage of the Outdoor Unit) This can be found on

the nameplate along with the outdoor voltage and the refrigerant.

Target Subcool

Manufacturer’s recommended subcooling for TXV/EXV

systems. This varies by manufacturer, and may also change depending

on weather conditions. Always charge to the equipment manufacturer’s

specifications when available. If no target subcooling is available then the

HVAC Guide will make a conservative estimate.

SL Pressure

(Suction Line Pressure) Connect the ASX14 to the suction

side service port. Select pressure mode on the ASX14 head. The system

must be stabilized before taking the measurements. Enter data manually

if you want to get pressure from your gauges. The analysis is only as good

as the measurements. The Fieldpiece ASX14 has better resolution than

most gauge sets.

SL Temp

(Suction Line Temperature) Measure near SL service port (within

6 inches). Use the ATC1 or ATC2 to get a good pipe temperature. The

clamp should be perpendicular to the pipe and should be securely seated

with the sensor in contact with the suction line. On a package unit make

sure you are at least 6 inches away from the compressor and not on the

hot gas discharge line.

LL Pressure

(Liquid Line Pressure) Connect the ASX14 to the liquid line

service port. Set the accessory head to measure pressure and ensure the

reading stabilizes before locking in the reading. Enter data manually if

you want to get pressure from your gauges. The analysis is only as good

as the measurements. The Fieldpiece ASX14 has better resolution than

most gauge sets.

LL Temp

(Liquid Line Temperature) Measure near the location that the LL

Pressure was taken. Use the ATC1 to get a good pipe temperature. The

clamp should be perpendicular to the pipe and should be securely seated

with the sensor in contact with the liquid line.

OD Dry Bulb

(Outdoor Dry Bulb Temperature) Clip a calibrated ATA1

to the inlet of the condenser (typically on the side of the condenser), in

the shade if possible. Note that the temperature of the air entering the

outdoor coil can be considerably different than the ambient temperature

due to recirculation of air exiting the unit. Determine the average tem-

perature of the air entering the condenser.

Cond Amps Draw

(Actual Condensing Unit Amp Draw) For a package

system this is the total amp draw of the unit. With a model HG3, use an

ACH4 amp clamp and take measurement automatically. To use another

amp clamp (such as the SC57) and for HG1s upgraded to an HG2, input

this measurement manually.

TrueFlow®

2

The TrueFlow® meter measures the airflow directly via a grid installed

in place of the filter (or other location that has all the indoor unit airflow

through it). For more information please visit www.energyconservatory.com.

TrueFlow®

Default: NO. If NO, skip ahead to the Customer ID. Answering

YES unlocks the inputs for this section.

Nom Ton

Nominal tonnage of the A/C system.

Grid Size

Default: 14 inches. Other selection: 20 inches.

Sup Plen Pres

TrueFlow® system operating pressure with the filter in-

stalled and no TrueFlow® grid. This is the normal supply operating pres-

sure (NSOP) and is measured using the static pressure probe included

with the TrueFlow® plate.

Flow Pressure

True Flow Supply Operating Pressure (TFSOP) using the

True Flow plate.

Sup Plen Pressure with Grid

TrueFlow® operating pressure with the

filter and TrueFlow® grid installed. This is the TF SOP and is measured

using the static pressure probe included with the TrueFlow® plate.