Fieldpiece ATC1 - Pipe Clamp Thermocouple User Manual

Advantages, Operation, Field calibration

background image

Models: ATC1 and ATC1R
Pipe Clamp K-type Thermocouple
Max: 257ºF (125°C)

OPERATOR’S MANUAL

Description

The ATC1 and ATC1R, K-type, pipe clamp ther-

mocouples, can be used to take temperatures of
pipes or any other cylindrical surface within their jaw
range. Using a pipe clamp thermocouple greatly
facilitates taking superheat or subcooling measure-
ments. Use the ATC1 for most A/C units and the
ATC1R for most residential and commercial refrig-
eration appliances. Both models can be used with
any thermometer accepting a K-type thermocouple.

Advantages

The sensor is virtually isolated from ambient con-

ditions, allowing the thermocouple to read the true
pipe temperature for as long as it is attached.

The sensor’s large surface area and increased

clamping force help the sensor reach the correct
temperature within 30 seconds.

Because the jaw is designed for HVAC/R, its

clamping ability lets you measure temperatures of
pipes that are fixed, at any angle, to walls or other
surfaces.

Operation

Plug the ATC1 or ATC1R into any thermometer

accepting a K-type thermocouple and adjust the
thermometer to the appropriate settings. Simply
clamp the thermocouple to a pipe and take the
measurement when the reading stabilizes.

Field calibration

Due to variances in the thermocouple wire and

other parts of the system, a field calibration should
be conducted before use. Field calibration typically
gives +/- 1ºF (0.5°C) overall accuracy. Refer to the
thermometer’s operating manual for calibration
instructions.

Specifications

ATC1 jaw range: 3/8” to 1 3/8” pipe diameter (OD)
ATC1R jaw range: 1/8” to 3/4” pipe diameter (OD)
Accuracy: +/- 4ºF (2°C) ; ±1°F (0.5°C) after field

calibration, 32 to 176ºF (0 to 80°C)

Temperature range: -50 to 257ºF (-46 to 125°C)
Thermocouple conductors: K-type nickel

chromium/nickel aluminum.

Probe insulation and clamp material: While cal-

ibration and atmosphere will affect maximum
useful temperature in applications, the wire insu-
lation and clamp material are designed to with-
stand a maximum continuous use at 257°F
(125°C).

Plug: K-type thermocouple male mini plug.
Typical stabilization time: less than 30 seconds.

Warranty

The ATC1 and ATC1R, K-type, clamp-on thermo-

couples are warranted against manufacturer’s
defects for one year. This warranty does not apply
to defects resulting from abuse, neglect, accident,
unauthorized repair, alteration, or unreasonable use
of the instrument. Any implied warranty arising out
of the sale of Fieldpiece's products including but not
limited to implied warranties of merchantability, and
fitness for purpose, are limited to the above.
Fieldpiece shall not be liable for incidental or conse-
quential damages.

Service

Return any defective ATC1 or ATC1R to

Fieldpiece for warranty service along with proof of
purchase. Contact Fieldpiece for out of warranty
repair charges.

www.fieldpiece.com

WARNINGS

The thermocouple and metal band may

become hot when testing hot pipes or cylinders.

Do not handle the thermocouple or the metal

band when hot.

!

!

v24

ATC1R

ATC1

PIPE

ATC1 SENSOR

HORIZONTAL AXIS

PIPE

EXAMPLE OF PROPER PLACEMENT
OF FIELDPIECE ATC1 PIPE CLAMP
THERMOCOUPLE ON HORIZONTAL
REFRIGERANT PIPE