Surge Protection of MP130 & MP133 modules

Models fitted with 2 or more MP130 or MP133 charger modules
must be fitted with MOVs across phases as follows:

 3 modules: 625VAC MOV fitted across S&T and T&R.

 2 modules: 625VAC MOV fitted across S&T.
 1 module: No MOV required.

MOVs may be fitted to the terminal blocks in conjunction with the
backplane loom wiring. MOV legs must be sufficient to

Earthed S-Phase Configuration

Some RST models required Earthed S phase, where an addition
earth link is made from the E terminal to the input S terminal.