Trap definitions – Dataprobe RSS Series User Manual
Page 43

V130816E.R1
RSS Series
Page 43
The value 3 is always returned from both the get and set commands to alert the operator that there is no data
for this command to return.
rss16PowerSupply1 1.3.6.1.4.1.1418.1.1.4
This read only variable returns the current status of the power supply 1 as an enumerated integer where:
1 = ok
2 = failed.
rss16PowerSupply2 1.3.6.1.4.1.1418.1.1.5
This read only variable returns the current status of the power supply 2 as an enumerated integer where:
1 = ok
2 = failed.
rss16Sync 1.3.6.1.4.1.1418.1.1.6
This read only variable returns the status of the synchronization channel (special models only) as an
enumerated integer where:
0 = ok
1 = fail
7.1.
Trap Definitions
ps1Failed specific-1
This trap is sent when ever power supply 1 fails. It carries not variable bindings.
ps1Ok specific-2
This trap is sent when ever power supply 1 returns to serves. It carries not variable bindings.
ps2Failed specific-3
This trap is sent when ever power supply 2 fails. It carries not variable bindings.
ps2Ok specific-4
This trap is sent when ever power supply 2 returns to serves. It carries not variable bindings.
switchChanged specific-5
This trap is sent when ever any or multiple switches are changed by any means. This trap will contain a
variable binding for each card in the chassis that has changed.
syncStatus specific-6
This trip is sent when ever the status of the chassis synchronization changes. It will contain the rss16Sync
variable. Only available in special models.