16 channel i/o control model ioc-16-r, Installation, Status and control connector pinouts – Dataprobe RSS Series User Manual
Page 33: 16 channel i/o control model ioc-16-r . 33, Status and control connector pinouts33

V130816E.R1
RSS Series
Page 33
5. 16 Channel I/O Control Model IOC-16-R
Item # 1340067
The IOC-16-R #1340067 provides wiring access for external contact control and switch card status monitoring. It
can be installed along with a IPC-16-R Network Control access card or with a IOC-16-R gang access card.
5.1.
Installation
The IOC-16-R installs in from the rear of the chassis in either of the two control
card slots only. If an IPC-R-16 card is also used, the IOC card should be installed
in 2
nd
control card slot, 3
rd
slot from the left in the rear of the chassis. Install the
card with the components facing left. The IOC-16-R may be inserted and removed
with the power on (hot insertion/removal) , but use caution as any contact wiring
connected to the IOC card may cause unintended switch card changes. Make
sure to use the screws provided to secure the card in the chassis before connecting
cables.
5.2.
Status and Control Connector Pinouts
The following pinouts detail the connections necessary for individual and gang
control of each A/B card, as well as the available status contacts.
Status
Status is dry relay contacts:
Common not connected to Normally Open (NO) = Switch in Position A
Common connected to Normally Open (NO) = Switch in Position B
Control
For control, momentarily connect the appropriate pin to Ground, for example, To switch Card Slot 2:
Connect Pin 2 to Ground to switch to A
Connect Pin 27 to Ground to switch to B
Use Pins 17 and 42 to switch all card slots simultaneously.
The complete pinout of these connectors follows on the next page.