beautypg.com

Dataprobe iPIO-2 Quick Start User Manual

Quick start guide, What’s included, Available online at

background image


IPIO quick start

© 2014 Dataprobe Inc.

V140120E

W

hat’s Included

iPIO-xx Unit

Network Cable

Quick Start Guide

A/C Power Supply

Available Online at

dataprobe.com/support

Complete Product Manual

Device Management Utility

Latest Firmware

Software Developer Tools

Connections

1.

Connect Network.

iPIO

supports 10/100 Ethernet using the cable supplied, or other suitable unshielded twisted pair (Cat

5) cabling. When power is connected to the iPIO, the green Activity LEDs on the network connector indicates when the
network connection is properly established.

2.

Connect Inputs.

(2 Connections per Channel)

Connect the inputs to the iPIO using the screw terminals.
Inputs can be either dry relay or switch contacts, or a +VDC
voltage (3 to 30 V), referenced to a common ground.
Screw terminals are removable for easy installation.
Terminals for each circuit are marked + and G. When
connecting dry relay contacts, the polarity is not significant.

3.

Connect Relays.

(3 Connections per Channel)

Relays are Form C. Connect to the Common (C),
Normally Closed (NC) and Normally Open (NO) as
marked. When the iPIO-8 relay is in the Open Condition,
the Common is connected to the Normally Open. In the
Closed state, the Common and Normally Closed are
connected.

4.

Connect Power.

Each unit is supplied with a n A/C

Power supply. Connect to suitable A/C source, then
power up the iPIO device. The iPIO-2 supports Power
over Ethernet (PoE). Consult the complete manual for more details.

.

Quick Start Guide

The iPIO is Factory set for Dry
Contact Input Only.
Prior to Connecting +VDC, Jumpers
must be configured.

See full manual or contact Dataprobe
Technical Support.

Relay Specifications

Rating (resistive)

0.5 A 120 VAC or
1 A 24 VDC

Max Carrying Current

2 A

Max Switching Power

60 AV, 24 W

Max Switching Voltage

120 VAC/60 VDC

Max Switching Current

1A

Life Expectancy

5 Million Operations Mech.
100K Oper. at rated load

This manual is related to the following products: