AMETEK SFA Series User Manual
Page 43

Sorensen SFA Series
Operation
Designator
Schematic
Symbol
Electrical
Chars.
Functional Description
8 Not
Used
9 Not
Used
10 IP
5V
Zin ~ 10k
Ω
Remote current programming using a 0-5 VDC source.
Do not exceed 13.3 VDC.
11
ISET
*
Zout ~
100
Ω
0-5 VDC (0-100%) front panel current control monitor output.
Minimum load resistance 10k
Ω.
12 SENSE
–
~ 1000
Ω to
neg (–)
output
terminal
Remote Sense (–) on 60 volts output units.
(For new installations, use J3, recommended only for
backward compatibility in existing systems.)
13 SENSE
+
~ 1000
Ω to
pos (+)
output
terminal
Remote Sense (+) on <60 volts output units.
(For new installations, use J3, recommended only for
backward compatibility in existing systems.)
14
ISO
TTL/CMOS
Zin ~ 2.2k
Ω
Isolated TTL/CMOS on/off control. A high state TTL/CMOS voltage
turns on the power supply, and a low state or open connection turns
the supply off.
15 Not
Used
16 IP
10V
Zin ~ 20k
Ω
Remote current programming using a 0-10 VDC source.
Do not exceed 25 VDC.
17 FAULT
Zout ~
100
Ω
Fault state output. A high state (approximately +10 VDC)
indicates a converter, temperature or bias supply fault, and
the LED on the front panel will illuminate.
18 S/D
FAULT
Zout ~
100
Ω
Shutdown fault. This terminal goes to high state in the event
of converter, temperature, overvoltage or bias supply fault. A
7 VDC to 13.3 VDC signal can be applied to this pin to
shutdown the output of the unit. An 8 VDC minimum output
signal is provided into a 10 k
Ω minimum load, in the event of
an internally generated shutdown.
19 V
MON
Zout ~
100
Ω
Output voltage monitor. 0-10 VDC equals to 0-100% rated
voltage. Minimum load resistance 10k
Ω.
M550292-01 Rev G
3-9