Electrical characteristics, Electrical characteristics -3 – AMETEK SFA Series User Manual

Page 21

background image

Sorensen SFA Series

Overview

M550292-01 Rev G

1-3

1.2.2

E

LECTRICAL

C

HARACTERISTICS

Parameter Specification

Input Power

Voltage (Standard)

208/220 VAC±10% (tested to 187-242 VAC)

Voltage (Options)

380/400 VAC±10% (tested to 342-440 VAC)
440/480 VAC±10% (tested to 396-528 VAC)

Frequency

47 to 63 Hz

Phases

3–phase, 3–wire plus ground. Not phase rotation sensitive.
Neutral not used.

Front Panel Meter Accuracy

Voltage

±0.5% of full-scale + 1 digit

Current

±0.5% of full-scale + 1 digit

Load Regulation

(Specified at no load to full load, nominal AC input)

Current

0.1% of maximum output current

Line Regulation

(Specified ±10% of nominal AC input, constant load)

Current

0.05% of maximum output current

Current Ripple

1% p-p of full-scale current

Transient Response

The output current will recover to within 1% of the set current
value within 1ms for a 10 to 100% or 100% to 10% step load
change

Output Slew Rate

(10-90% current, full resistive load, nominal AC input):
250A/ms (400A/ms typical) rise, 200A/ms typical fall;

160V models, 87A/ms/5kW (145A/ms/5kW typical), rise,
60A/ms, typical, fall

100V models, 190A/ms/5kW (238A/ms/5kW typical), rise,
104A/ms, typical, fall

Current Overshoot

Maximum 8% of full-scale for 0 to 100% change into a resistive
load

Stability

±0.05% of set point after 8–hr. warm-up at fixed line, load, and
temperature.

Remote Control/Monitor

On/Off control via contact closure, 6-120 VDC or 12-240 VAC,
and TTL or CMOS switch, current monitor, OCP limit set,
summary fault status

Power Factor

>0.9 typical for 208/220VAC input
>0.78 typical for 380/400VAC input
>0.7 typical for 440/480VAC input