SET DMX RESPONSE

DMX Response sets a delay time before DMX Control Mode settings are acted on.

Setting a response delay of a few seconds would prevent unintended fixture relay

state changes in the event of a short accidental change in DMX level.

NOTE: from firmware revision 0.00.100, DEC holds last valid DMX level if DMX is

interrupted.

Response Delay Values are:

No Delay (default), 1, 2, 5, 10, 15, 20, 30, 60 seconds.

SET TEMP UNITS

Choose to display temperature values in Celsius or Fahrenheit (default Celsius)

Note that temperature settings must be entered in Celsius.

SET TEMP RANGES

Set three temperature trigger points for Bottom, Top and Trip temperatures, in °C.

SET TEMP LOWER (minimum temperature to be maintained)

(default 0°C, permissible range 0-10°C).

SET TEMP UPPER (maximum desired temperature)

(default 40°C, permissible range 35-50°C).

SET TEMP TRIP (temperature at which load will be isolated – see note)

(default 60°C, permissible range 55-70°C).

Note: A thermal emergency is when enclosure ventilation fails with the lamp on, in which case the
temperature will rise very quickly. To avoid nuisance tripping we recommend setting a higher Trip

temperature, 60°C or above.

SET MAX HUMIDITY

(default 80%, permissible range 50-90%).

Set target maximum relative humidity level. This should be set at or a few % higher than

the normal high humidity levels expected on site.

SET LAMP ON POINT

The lamp current at which DEC detects the luminaire/luminaire lamp is running. Default is

1 Amp, which allows for equipment fans and power supplies to run without changing the

air in the enclosure. Lamp on point may be set in 0.2 Amp increments between 0.2 Amps

and 2.0 Amps.

RESET LAMP HOURS

Reset each time you change the lamp in the luminaire/luminaire.

Make this a part of your maintenance instructions.