RTD input
RTD input
RTD input
RTD inputssss
To use as RTD input lift the lid (see 3.1) and place a 5.11kΩ / 0.1% resistor into the header on Rt:
Connect the RTD element between ground and the RTD input.
5.6.1
5.6.1
5.6.1
5.6.1
Configuration
Configuration
Configuration
Configuration
Configure the following items with the software:
•
Name, this name must be unique and can not be used with any other input or output.
Default set as RTD1 to RTD8.
•
The unit for the input feedback:
•
°C, degrees Celsius
•
°F, degrees Fahrenheit
•
The RTD element:
•
PT1000
•
NI1000
•
PT100
•
Lower limit threshold.
•
Upper limit threshold.
•
Minimal change (hysteresis).
•
The Analog Inputs can generate messages with value and unit when:
•
The upper limit + hysteresis is reached
•
The lower limit – hysteresis is reached
•
The state recovers between the upper and lower limit +/- hysteresis
Note:
Note:
Note:
Note: The threshold/hysteresis values are limited to 5 digits with a maximum of 2 decimals.