Voltage thd alarm – CIRCUTOR computer SMART III-Fast Series User Manual
Page 96

5�22�-VOLTAGETHDALARM
InthispointthethresholdsabovewhichtheVoltage
THDalarm(
E08
)isactivatedcanbeconfigured�
Thealarmmustbeenabled(
The programmed values are useful for the 3
phaseswhichtheunitmeasures�
Pressthe
keytoentereditingmode�Itis
identifiedbythe
symbolandtheblinkingof
thedigitstobemodified�
Theparameterstobeconfiguredare:
The
Lo
value : whentheunitexceedsthisvaluefor30minutes,alarm
E08
is
triggered,andifalarm
E11
isenabled,the
SMART III FASTunitentersNo Connection
statusandactivates
alarm
E11
�
The
HI
value: iftheunitexceedsthisvaluefor30seconds,alarm
E08
istriggered,
andifalarm
E12
isenabled,the
SMART III FASTunitentersDisconnection statusand
activates
alarm
E12
�
Iftheunitfallsbackunderthe
Lo
valuefor10minutes,itdeactivatesthealarmsandreturns
tothenormaloperatingstatus�
Inthe
No Connectionstatus,theunitdoesnotconnectthestages,butalsodoesnot
disconnectthemiftheoperationrequiresit�
Inthe
Disconnectionstatus,itdisconnectsthestagesanddoesnotallowthemtoconnect�
The
keyincreasesthedigitvalue�
The
keydecreasesthedigitvalue�
The
keyskipstothepreviousdigit�
The
keyskipstothenextdigit�
Press
tovalidatethedata;the
symboldisappearsfromthedisplay�
Lo
Valueand
HI
Value:
Maximum value: 99%
Minimum value: 1%
96
Computer SMART III FAST
Instruction Manual