CIRCUTOR computer SMART III-Fast Series User Manual
Page 65

Example:IfyouseeCurrent1=1,Current2=5andCurrent3=3,thismeansthat:
Current1isassignedtovoltage1inthedirectdirection,current2isassignedtovoltage2inthereverse
directionandcurrent3isassignedtovoltage3inthedirectdirection�
Table 20:Modbus memory map: programming variables (Table 6)
Status of the stages
Configuration variable
Address
Valid data margin
Default value
C1
1110
0(Auto),
1(On),
2(OFF),
3(OnNc)
0
C2
1111
0
C3
1112
0
C4
1113
0
C5
1114
0
C6
1115
0
C7
1116
0
C8
1117
0
C9
1118
0
C10
1119
0
C11
111A
0
C12
111B
0
Table 21:Modbus memory map: programming variables (Table 7)
Voltage level
Configuration variable
Address
Valid data margin
Default value
Voltagelevel
1121
0(Lowvoltage)
1(Medium/Highvoltage)
0
Table 22:Modbus memory map: programming variables (Table 8)
Display
Configuration variable
Address
Valid data margin
Default value
Lighting(Backlight)
1125
0(Comesonwhenpressingakey)
1(ON),2(OFF)
0
Lightinglevel
1126
0-10(Value%/10)
7
Language
1127
0(Spanish),1(English)
0
Advancedsetup
1128
0(OFF),1(ON)
0
Analoguebar
1129
0(No),1(Current),2(ITHD)
3(Connectedpower)
0
Table 23:Modbus memory map: programming variables (Table 9)
Target cos φ
Configuration variable
Address
Valid data margin
Default value
Targetcosφ1
1130
0-100(Valuex100)
100
Targetcosφ2
1131
100
Targetcosφ3
1132
100
Targetcosφ4
1133
100
Targetcosφ1type
1134
0(Capacitive)
1(Inductive)
1
Targetcosφ2type
1135
1
Targetcosφ3type
1136
1
Targetcosφ4type
1137
1
65
Instruction Manual
Computer SMART III FAST