Voltage alarms – CIRCUTOR computer SMART III-Fast Series User Manual
Page 94

5�20�-VOLTAGEALARMS
Inthispointthephase-phasevoltagethresholds
abovewhichtheovervoltagealarm(
E05
)andthe
novoltagealarm(
E06
)shouldbetriggeredcanbe
configured�
Thealarmmustbeenabled(
Pressthe
keytoentereditingmode�Itis
identifiedbythe
symbolandtheblinkingof
thedigitstobemodified�
Inordertoavoidpossiblefalseactivationsofsaidalarms,theyhaveapredefineddelayof5
seconds�
Theparameterstobeconfiguredare:
The
value of the overvoltage alarm:
HI
�
The
value of the no voltage alarm:
LO
�
Whenanyofthetwoalarmsaretriggered,theunitentersthe
Disconnectionstatusand
disconnectsallthestages�Theunitdoesnotreturntoitsnormaloperatingstatusuntilthe
causeforthealarmdisappears�
The
keyincreasesthedigitvalue�
The
keydecreasesthedigitvalue�
The
keyskipstothepreviousdigit�
The
keyskipstothenextdigit�
Press
tovalidatethedata;the
symboldisappearsfromthedisplay�
Overvoltage alarm:
Maximum
value:
99999V
Minimum
value:
0V
No voltage alarm:
Maximum
value:
99999V
Minimum
value:
0V
Ifthevalueenteredislowerthantheminimumvalueorhigherthanthemaximumvalue,
thebacklightofthedisplayflashesandthevalueenteredisreplacedwiththeminimumor
maximumvalue,orwiththelastvaluevalidated�
Pressthe
keytoaccessthenextprogrammingstep�
Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,
�
94
Computer SMART III FAST
Instruction Manual