CIRCUTOR computer SMART III-Fast Series User Manual
Page 74

Code
Description
P04
Errorinthemeasurementofthelargestcapacitor�
P05
Nocapacitorsfound�
P06
Incorrectmeasurementofthenumberofcapacitors�
P07
Incorrectmeasurementoftheratioofthefirstcapacitor�
P08
Possibleerrorintheprogramcalculated�
P09
C/Koutofrange�
Inthecaseofthe
P00
error,i�e�,whencapacitorshavebeendeactivatedbyaleakagecurrent
alarmorforcedintheOn/Off/AutoConfiguration,theP&Pfunctionwillnotbestarteduntilthe
problemisresolved�
ThePlug&Playfunctionisdesignedtoassistwiththeinstallationofthereactiveenergy
compensationsystem,withtheinitialconfigurationoftheregulatororwhentherearechanges
inthesystem(newregulator,newcabling,newstage,etc�)�Forthisreason,itisnecessary
priortothePlug&Playfunctiontosolvethepossibleproblemswithfaultycapacitorsbymeans
ofmaintenanceorreplacement,aswellastoconfigureallthestagesinAutomode,asthey
comebydefault�
Conditions for the correct operation of the Plug&Play function:
Thesystemshouldbemaintainedwithaninductivecosineof0�62to0�99
throughouttheprocess�
Thepowerinthesystemshouldbestable�Anymajorloadchanges(>10%
inlessthan20seconds)wouldresultinanincorrectcalculationofthecapacitor
powerratings�
Theremustbeenoughcurrentinthesystem,above100mAACatthe
regulatorintake�
Iftheloadisunbalanced,thecorrectoperationofthePlug&Playfunctionwill
dependonthephasetowhichthecurrenttransformerisconnected�
I
OncethePlug&Playfunctionisfinished,theprimaryofthecurrenttransformer
needstobeconfiguredinorderfortheunittomeasurethecurrentandthe
powerscorrectly�
Pressthe
keytomoveontothenextconfigurationpoint�
Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,
�
74
Computer SMART III FAST
Instruction Manual