Status of the capacitors, Status of the unit, Auto – CIRCUTOR computer SMART III-Fast Series User Manual
Page 31: On nc

4�4�1� STATUS OF THE CAPACITORS
Figure 13: Status of the capacitors�
Thisareashowsthestatusoftherelays(stages)oftheunit,andthusofthecapacitorscon-
nectedtoit�
Thepossiblestatesare:
Nothingisdisplayedifthestageisnotconnectedandconfiguredas
AUTO
�
The iconisdisplayedifthestageisconnectedandconfiguredas
AUTO
�
The iconisdisplayedwiththebottomstaticbarifthestageisconnectedandcon-
figuredas
On
�
The
iconisdisplayedwiththebottombarblinkingifthestageisconnectedand
configuredas
On NC
�
Onlythestaticbottombarisdisplayedifthestageisdisconnectedandconfiguredas
OFF
�
Onlytheblinkingbottombarisdisplayedifthestageiscancelledbytheleakagecur-
rentalarm
E15
�
Inthesetupmenu(
)thestatusofthestagesisselectedfrom
thefollowingoptions:
AUTO
:Thestatusofthestagedependsontheoperationperformedbytheunit�
On
:StageforcedtoON,alwaysconnected�
OFF
:StageforcedtoOFF,alwaysdisconnected�
On NC
:StageforcedtoON,alwaysconnectedbutthesystemdoesnottakeinto
accountitsconnectedpower�
Bydefault,allthestagesareconfiguredas
AUTO
�
4�4�2� STATUS OF THE UNIT
Thisareadisplaysthestatusoftheunitinaccordancewiththefollowingicons:
Theunitisinmeasurementandregulationmode�
Theunitdoesnotmeasureorregulate�
Indicatesthatyouareinthesetupmenu�
Indicatesthatyouareinthetestmenu�
Indicatesthat,withinthesetupmenu,youareineditingmode�
Indicatesthatyouareviewingtheinstantaneousvalue�
Indicatesthatyouareviewingthemaximumvalue�
Indicatesthatyouareviewingtheminimumvalue�
31
Instruction Manual
Computer SMART III FAST