CIRCUTOR computer SMART III-Fast Series User Manual
Page 64

B�-Programming variables
Thefollowingfunctionsareimplementedforthesevariables:
Function 04:readinglogs�
Function 10:Writingmultiplelogs�
Table 15:Modbus memory map: programming variables (Table 1)
Unit parameters
Configuration variable
Address
Serialnumber
(1)
1000-1003
Framenumber
(1)
1010-1013
Version
(1)
1020-1021
Hardwarelog
(1)
1030-1033
(1)
Theparametersoftheunithaveonlyimplemented
function 04�
Table 16:Modbus memory map: programming variables (Table 2)
RS-485 Communications
Configuration variable
Address
Valid data margin
Default value
Peripheralno�
1071
1to254
1
Speed
1072
0(9600),1(19200)
1
Parity
1073
0(none),1(odd),2(even)
0
Length
1074
0(8bits),1(7bits)
0
Stopbits
1075
0(1bits),1(2bits)
0
Table 17:Modbus memory map: programming variables (Table 3)
CPC-NET communications
Configuration variable
Address
Valid data margin
Default value
Speed
1082
0(9600),1(19200),2(38400)
2
Parity
1083
0(none),1(odd),2(even)
0
Stopbits
1085
0(1bits),1(2bits)
0
Table 18:Modbus memory map: programming variables (Table 4)
Transformation ratios
Configuration variable
Address
Valid data margin
Default value
Currentprimary
1090
1-10000
5
Currentsecondary
1091
0(1A),1(5A)
1
Voltageprimary
1092-1093
1-99999
1
Voltagesecondary
1094-1095
1-99999
1
Table 19:Modbus memory map: programming variables (Table 5)
Connection type
Configuration variable
Address
Valid data margin
Default value
Connectiontype
1100
0(3U�3C),1(3U�1C),2(2U�1C)
0
Phase
(1)
1101
1to6(Table41)
1
Current1
/1/2
1102
1(Phase1direct),2(Phase2direct),
3(Phase3direct),4(Phase1re-
verse),
5(Phase2reverse),6(Phase3
reverse),
1
Current2
(1)(2)
1103
2
Current3
(1)(2)
1104
3
(1)
Onlyusedwhentheconnectiontypeisotherthan3U�3C�
(2)
Indicatestherelationshipbetweentheassignedvoltageandthecurrentdirection�
64
Computer SMART III FAST
Instruction Manual