Modbus memory map – CIRCUTOR computer SMART III-Fast Series User Manual
Page 60
4�9�3� MODBUS MEMORY MAP
A�-Measurement Variables
Forthesevariables
Function 04isimplemented:readinglogs�
TheModbusaddressesofallthetablesarehexadecimal�
Table 12: Modbus memory map: measurement variables (Table 1)
Parameter
Instantaneous Maximum Minimum
Units
L1Phasevoltage
00-01
200-201
300-301
V/100
L1Current
02-03
202-203
302-303
mA
L1Activepower
04-05
204-205
304-305
W
L1InductiveReactivePower
06-07
206-207
306-307
varL
L1CapacitiveReactivePower
08-09
208-209
308-309
varC
L1Reactivepower
0A-0B
20A-20B
30A-30B
var
L1Apparentpower
0C-0D
20C-20D
30C-30D
VA
L1ReactivePowerConsumed
0E-0F
20E-20F
30E-30F
var
L1ReactivePowerGenerated
10-11
210-211
310-311
var
L1PowerFactor
(1)
12-13
212-213
312-313
-
L1Cosφ
(1)
14-15
214-215
314-315
-
L1kWsign
(1)
16-17
-
-
+1or-1
L1kvarsign
(1)
18-19
-
-
+1or-1
L2Phasevoltage
1A-1B
21A-21B
31A-31B
V/100
L2Current
1C-1D
21C-21D
31C-31D
mA
L2Activepower
1E-1F
21E-21F
31E-31F
W
L2InductiveReactivePower
20-21
220-221
320-321
varL
L2CapacitiveReactivePower
22-23
222-223
322-323
varC
L2ReactivePower
24-25
224-225
324-325
var
L2ApparentPower
26-27
226-227
326-327
VA
L2ReactivePowerConsumed
28-29
228-229
328-329
var
L2ReactivePowerGenerated
2A-2B
22A-22B
32A-32B
var
L2PowerFactor
(1)
2C-2D
22C-22D
32C-32D
-
L2Cosφ
(1)
2E-2F
22E-22F
32E-32F
-
L2kWsign
(1)
30-31
-
-
+1or-1
L2kvarsign
(1)
32-33
-
-
+1or-1
L3Phasevoltage
34-35
234-235
334-335
V/100
L3Current
36-37
236-237
336-337
mA
L3ActivePower
38-39
238-239
338-339
W
L3InductiveReactivePower
3A-3B
23A-23B
33A-33B
varL
L3CapacitiveReactivePower
3C-3D
23C-23D
33C-33D
varC
L3ReactivePower
3E-3F
23E-23F
33E-33F
var
L3ApparentPower
40-41
240-241
340-341
VA
L3ReactivePowerConsumed
42-43
242-243
342-343
var
L3ReactivePowerGenerated
44-45
244-245
344-345
var
L3PowerFactor
(1)
46-47
246-247
346-347
-
L3Cosφ
(1)
48-49
248-249
348-349
-
L3kWsign
(1)
4A-4B
-
-
+1or-1
L3kvarsign
(1)
4C-4D
-
-
+1or-1
60
Computer SMART III FAST
Instruction Manual