Status of the stages, 5�12�- status of the, Stages – CIRCUTOR computer SMART III-Fast Series User Manual
Page 86: Auto, On nc

Pressthe
keytoaccessthenextprogrammingstep�
Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,
�
5�12�-STATUSOFTHESTAGES
Thisparameterisrepeatedforeachofthe6or12
possiblestages,offeringtheopportunitytoforce
theirstatuswithoutpayingattentiontotheoperation
performedbytheactualunit�
Inordertoidentifywhichofthe12stagesisbeing
configured,thescreenshows
C1
,
C2
,etc�
Theconfigurationoptionsforeachstageareasfollows:
AUTO
:Thestatusofthestagedependsontheoperationperformedbytheunit�
On
:StageforcedtoON,alwaysconnected�
OFF
:StageforcedtoOFF,alwaysdisconnected�
On NC
:StageforcedtoON,alwaysconnectedbutthesystemdoesnottakeinto
accountitsconnectedpower�
Bydefault,allthestagesareconfiguredas
AUTO
�
Onthemeasurementscreens,theforcedstatesofthestagesareshownbyactivatingthe
bottomlineofthecapacitorstatusbar�(
“4�4�1� STATUS OF THE CAPACITORS”
)
Pressthe
keytoentereditingmode�Itisidentifiedbythe
symbolandtheblinking
ofthedigitstobemodified�
The
keyshowsthenextoption�
The
keyshowsthepreviousoption�
The
keyskipstothepreviousstage�
The
keyskipstothenextstage�
Press
tovalidatethedata;the
symboldisappearsfromthedisplay�
Pressthe
keytoaccessthenextprogrammingstep�
Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,
�
86
Computer SMART III FAST
Instruction Manual