CIRCUTOR computer SMART III-Fast Series User Manual
Page 66

Table 24:Modbus memory map: programming variables (Table 10)
C/K factor
Configuration variable
Address
Valid data margin
Default value
C/Kfactor
1138
0-100(Valuex100)
100
Table 25:Modbus memory map: programming variables (Table 11)
Program
Configuration variable
Address
Valid data margin
Default value
Program
1139
1111-1999
1111
Operationtype
113A
0(FCP),1(Total),2(Sim)
0
Table 26:Modbus memory map: programming variables (Table 12)
No� of stages
Configuration variable
Address
Valid data margin
Default value
No�ofstages
113B
0-6(ComputerSMARTIIIFAST6)
0-12(ComputerSMARTIIIFAST12)
6
12
Table 27:Modbus memory map: programming variables (Table 13)
Connection and reconnection time
Configuration variable
Address
Valid data margin
Default value
Connectiontime
113C
0-999networkcycles
10
Reconnectiontime
113D
0-999networkcycles
50
Table 28:Modbus memory map: programming variables (Table 14)
Alarm: Voltage THD
Configuration variable
Address
Valid data margin
Default value
LowValue
1140
0-100%
5
HiValue
1141
0-100%
10
Table 29:Modbus memory map: programming variables (Table 15)
Alarm: Current x I THD
Configuration variable
Address
Valid data margin
Default value
LowValue
1142
0-100%
4
HiValue
1143
0-100%
5
Table 30:Modbus memory map: programming variables (Table 16)
Alarm: Temperature
Configuration variable
Address
Valid data margin
Default value
LowValue
1144
0-80ºC
55
HiValue
1145
0-80ºC
70
Table 31:Modbus memory map: programming variables (Table 17)
Alarm: Leakage Current
Configuration variable
Address
Valid data margin
Default value
Searchfortheresponsiblestage
1146
0(OFF),1(ON)
0
Value
1147
10-1000mA
300
Stagesenabled
1148
0(No),1(Yes)
0
Table 32:Modbus memory map: programming variables (Table 18)
Alarm: Cos φ
Configuration variable
Address
Valid data margin
Default value
ValueofCosφ
1149
80-100(Valuex100)
95
Currentvalue
114A
0-9999A
20
TypeofCosφ
114B
0(Capacitive),1(Inductive)
1
66
Computer SMART III FAST
Instruction Manual