Technical details, 9technical details, 1 technical details – Pilz PDP67 F 8DI ION HP User Manual
Page 33

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
9-1
9.1
Technical details
9
Technical details
9
9000
Technical details
Technical details
9-
9.1
Technical details
9100
Technical details
9-
][Technische Daten_PDP_DI
Technical details
Application range
Standard/Failsafe
Electrical data
Internal supply voltage
Supply
Supply voltage U
B
DC
24 V
Voltage tolerance
-30 %/+25 %
Power consumption at U
B
1.2 W
Inputs
Number
8
Input voltage
24 V DC
Input current
3.0 mA
Potential isolation between input and internal bus voltage
yes
Outputs (configurable as semiconductor outputs or
test pulse outputs)
Infeed for
Load Supply
Voltage
24 V DC
Voltage tolerance
-30 %/+25 %
Max. continuous current that the external power supply
must provide
4.0 A
Max. unit fuse protection F1
4 A
Max. unit fuse protection F1 in according with UL508
4 A
Number of positive-switching single-pole semiconductor
outputs
8
Short circuit-proof
yes
Potential isolation between semiconductor output and in-
ternal bus voltage
yes
Potential isolation between semiconductor output and in-
put
no
Typ. output current at “1” signal and rated voltage of sem-
iconductor output
0.50 A
Permitted current range
0.00 - 0.60 A
Residual current at “0” signal
0.02 mA
Permitted loads
inductive, capacitive, resistive
Max. internal voltage drop
200 mV
Terminal voltage when switching off inductive loads
-45 V
Number of test pulse outputs
8
Number of outputs that can be configured as test pulses
8
Max. output current at “1” signal
0.50 A
Short circuit-proof
yes
Max. cable runs between test pulse output and input
20 m
Hardware processing times
Max. processing time for input when signal changes from
“1” to “0”
1.000 ms
Max. processing time for input when signal changes from
“0” to “1”
1.200 ms
Min. processing time for input when signal changes from
“1” to “0”
0.50 ms
Min. processing time for input when signal changes from
“0” to “1”
0.70 ms