Function description, Unit properties, 1 operation – Pilz PDP67 F 8DI ION HP User Manual

Page 13: 1 inputs, 2 outputs, 4function description, 1 unit properties

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-1

4.1

Unit properties

4

Function description

4

4000

Function description

Function description

4-

4.1

Unit properties

4100

Unit properties

4-

4.1.1

Operation

Operation

4-

Funktionen_PDP_DI_Konfiguration

The functions of the inputs and outputs are configured in the system

software.

4.1.1.1

Inputs

Inputs

4-

Funktionen_PDP_DI_Eingänge

Single and dual-channel sensors can be connected to the inputs, with

or without test pulses.

Input signals must show a “High” (“1” signal) of 15 VDC (+15 ... +30 VDC)

and a “Low” (“0” signal) of 0 VDC (-3 ... +5 VDC).

The input status is signalled to the control system via the bus.

Green LEDs indicate the status of the inputs.

Test pulses can be used to check the inputs for shorts across contacts

and correct functionality.

4.1.1.2

Outputs

Outputs

4-

Funktionen_PDP_DI_Ausgänge

The outputs can be used as standard outputs, as test pulse outputs or

as 24 VDC outputs.

The test pulse outputs are suitable for testing the sensor wiring. All safe-

ty-related inputs must operate in accordance with the failsafe principle

(on switching off).

Two test pulses are available on each plug-in connector; these test puls-

es are permanently assigned to the inputs. The assignment of the test

pulses to the inputs cannot be changed in the system software's config-

urator.

If the test pulse outputs are not being used, they can be configured as

standard outputs or 24 VDC outputs in the system software's configu-

rator.