beautypg.com

Terminal configuration, 6wiring, 2 terminal configuration – Pilz PSSu XB F -T User Manual

Page 25

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-3

6.2

Terminal configuration

6

Wiring

6.2

Terminal configuration

6200

Terminal configuration

6-

][Klemmenbelegung XB

Base module

Terminal configuration

Screw terminals:
PSSu BP 2/16S
PSSu BP 2/16S-T

Cage clamp terminals:
PSSu BP 2/16C
PSSu BP 2/16C-T

Without C-rail:

11-21: 0 V periphery supply
(11-21 linked internally)

12-22: 0 V periphery supply
(12-22 linked within the base module)

13-23: +24 V periphery supply
(13-23 linked within the base module)

14-24: +24 V periphery supply
(14-24 linked internally)

31-41-32-42-33-43-34-44 not con-
nected

Screw terminals:
PSSu BP-C 2/16S
PSSu BP-C 2/16S-T

Cage clamp terminals:
PSSu BP-C 2/16C
PSSu BP-C 2/16C-T

With C-rail:

11-21: 0 V periphery supply
(11-21 linked internally)

12-22: 0 V periphery supply
(12-22 linked within the base module)

13-23-33-43: C-rail supply
(13-23-33-43 linked within the base
module)

14-24: +24 V periphery supply
(14-24 linked internally)

31-41-32-42-34-44 not connected

21

11

22

12

23

13

24

14

41

31

42

32

43

33

44

34

21

11

22

12

23

13

24

14

41

31

42

32

43

33

44

34