8technical details, 1 technical details – Pilz PSSu E F PS-P User Manual
Page 34

8.1
Technical details
8
Technical details
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
8-2
Shock stress
EN 60068-2-27 base type, T-type
15g base type, T-type
11 ms base type, T-type
EN 60068-2-29 base type, T-type
10g base type
25g T-type
16 ms base type
6 ms T-type
Protection type in accordance with EN 60529 base type,
T-type
Mounting (e.g. cabinet)
IP54 base type, T-type
Housing
IP20 base type, T-type
Terminals
IP20 base type, T-type
Airgap creepage in accordance with EN 60664-1 base
type, T-type
Overvoltage category
II base type, T-type
Pollution degree
2 base type, T-type
Environmental data for railway applications
Application site in accordance with EN 50125-3 R-type
Track area (1m – 3m) R-type
Application site in accordance with EN 61373 R-type
Category 1, Class A + B R-type
Climatic suitability
50125-1, 50125-3, 50155
Max. operating height above sea level
2,000 m R-type
Ambient temperature in accordance with EN 50155 R-type -40 ... +70 °C R-type
Ambient temperature in accordance with EN 50125-1
R-type, EN 50125-3 R-type
-40 ... +70 °C R-type
Shock stress EN 50125-3 R-type
2 g R-type
11 ms R-type
Vibration to 50125-3 R-type
0.23 g R-type
5 ... 2,000 Hz R-type
Shock stress EN 61373 R-type
5 g R-type
30 ms R-type
Broadband noise in accordance with EN 61373 R-type
Max. acceleration
0.79 g RMS R-type
Frequency
5 ... 150 Hz R-type
Protection type in accordance with EN 60529 R-type
Mounting (e.g. cabinet)
IP51 R-type
Housing
IP20 R-type
Terminals
IP20 R-type
Airgap creepage in accordance with EN 50124-1 R-type
Overvoltage category
OV2 R-type
Pollution degree
PD1 R-type
Supply interruptions in accordance with EN 50155 R-type
S2, C1, C2 R-type
Mechanical data
Housing material
Front
PC
Bottom
PC
Coding
PA
Environmental data