Page 14: 2 status byte, Configuration, Pssu assignment in system environment a

Function description
Operating Manual PSSu E S 4DI-D
1001322-EN-04
14
Configuration
PSSu assignment in system environment A
It is not necessary to configure ST inputs in the PSSuniversal Configurator on the
PSS WIN-PRO system software, but ST modules can be selected and displayed.
The ST process image can be optimised by combining adjacent bits of the same type into
bytes.
If the status byte is configured, the ST process image cannot be optimised.
Further information on configuration is available in the PSSuniversal Configurator's online
help.
Addresses in the process image
The module occupies 4 consecutive bit addresses in the process image.
Configuration
SafetyBUS p
Standard bus system
FS-PII
ST-PII
ST-PIO
Without status byte
- - -
4 Bit
- - -
With status byte (“S“)
- - -
8 + 4 Bit
- - -
Information
Further information on the structure and contents of the status byte can be
found under “Operation”.
Status byte
The status byte contains the information on overload and overtemperature.
Structure and contents of the status byte:
Bit number Signal
Key
0
0
No overload on supply output S1
1
Overload on supply output S1
1
0
No overload on supply output S2
1
Overload on supply output S2
2
0
Reserved
1
Reserved
3
0
Reserved
1
Reserved
4
0
No temperature error
1
Temperature error: too warm
5
0
Switch-off temperature not reached.
1
Temperature error: too hot. Supply outputs switch off.