beautypg.com

1 dac raw value, 2 hardware calibration, Dac raw value – Pilz PSSu E S 2AO U User Manual

Page 14: Hardware calibration

background image

Function description

Operating Manual PSSu E S 2AO U(­T)
21423­EN­03

14

Analogue value and typical digital value with a voltage range of 0 ... +10 V plus de­
fault values:

Analogue value of voltage

Decimal digital value

0 V

0

5 V

16 384

10 V

32 767

5 V

6 V

7 V

8 V

9 V

4 V

3 V

2 V

1 V

0 V

10 V

32 767

29 490

26 214

22 937

19 660

16 384

13 107

9 830

6 553

3 277

0

Analogue value and typical digital value with a voltage range of ­10 V ... +10 V plus
default values:

Analogue value of voltage

Decimal digital value

­10 V

­32 767

­5 V

­16 384

0 V

0

5 V

16 384

10 V

32 767

0 V

2 V

4 V

6 V

8 V

-2 V

-4 V

-6 V

-8 V

-10 V

10 V

32 767

26 214

19 660

13 107

6 553

0

-6 553

-13 107

-19 660

-26 214

-32 767

4.2.1.1

DAC raw value

You can configure each channel so that the raw value is transferred directly to the DA con­
verter, without calibration or scaling.

4.2.1.2

Hardware calibration

Each channel is calibrated ex­works in order to correct component dispersion and other in­
fluences.

The range is divided so that zero is assigned the value 0 and the end point is assigned the
value 4095

(0FFF

H

).

This manual is related to the following products: