1 dac raw value, 2 hardware calibration, Dac raw value – Pilz PSSu E S 2AO U User Manual
Page 14: Hardware calibration

Function description
Operating Manual PSSu E S 2AO U(T)
21423EN03
14
Analogue value and typical digital value with a voltage range of 0 ... +10 V plus de
fault values:
Analogue value of voltage
Decimal digital value
0 V
0
5 V
16 384
10 V
32 767
5 V
6 V
7 V
8 V
9 V
4 V
3 V
2 V
1 V
0 V
10 V
32 767
29 490
26 214
22 937
19 660
16 384
13 107
9 830
6 553
3 277
0
Analogue value and typical digital value with a voltage range of 10 V ... +10 V plus
default values:
Analogue value of voltage
Decimal digital value
10 V
32 767
5 V
16 384
0 V
0
5 V
16 384
10 V
32 767
0 V
2 V
4 V
6 V
8 V
-2 V
-4 V
-6 V
-8 V
-10 V
10 V
32 767
26 214
19 660
13 107
6 553
0
-6 553
-13 107
-19 660
-26 214
-32 767
4.2.1.1
DAC raw value
You can configure each channel so that the raw value is transferred directly to the DA con
verter, without calibration or scaling.
4.2.1.2
Hardware calibration
Each channel is calibrated exworks in order to correct component dispersion and other in
fluences.
The range is divided so that zero is assigned the value 0 and the end point is assigned the
value 4095
D
(0FFF
H
).