beautypg.com

2 terminal configuration, Terminal configuration – Pilz PSSu E AI SHT2 User Manual

Page 19

background image

Wiring

Operating Manual PSSu E AI SHT2
1003113­EN­01

19

}

On base modules with screw terminals:

If you use a multi­strand cable to connect the I/Os, it is recommended that you use
ferrules conforming to Parts 1 and 2 of DIN 46228, 0.14 ... 1.5 mm

2

, Form A or C,

although this is not essential. To crimp the ferrules you can use crimp pliers (crimp
form A or C) conforming to EN 60947­1, such as the PZ 1.5 or PZ 6.5 from
Weidmüller, for example.

Maximum torque setting: 0.8 Nm

}

Use copper wiring.

6.2

Terminal configuration

Base module

Terminal configuration

Screw terminals:
PSSu BP 1/8S
PSSu BP 1/8S­T

Cage clamp terminals:
PSSu BP 1/8C
PSSu BP 1/8C­T

Without C­rail:

11: Output O0+

21: Output O1+

12: Output O0­

22: Output O1­

13­23: Shield connection
(13­23 linked within the base
module)

14: Input I0

24: 0 V analogue

21

11

22

12

23

13

24

14