beautypg.com

4 function description, 1 module features, 1 function description – Pilz PSSu E AI SHT2 User Manual

Page 11: Section 4, Function description, Module features, 4function description

background image

Function Description

Operating Manual PSSu E AI SHT2
1003113­EN­01

11

4

Function Description

4.1

Module features

4.1.1

Function description

The electronic module PSSu E AI SHT2 contains two shunts for scaling an input current I

I0

(connection I0). The two current outputs I

O0

 (connection O0+) and I

O1

 (connection O1+) are

evaluated by analogue current inputs.

Scaling is applied during evaluation via an analogue input module with an input resistance
of 115 Ohm, (e.g. PSSu E F AI I)

}

Scaling factor with resistance R

1

 + R

 = 10,150 Ohm (connections O0+/O0­):

I

O0

 : I

I0

 = 1:10

}

Scaling factor with resistance R

2

 = 6,750 Ohm (connections O1+/O1­):

I

O1

 : I

I0

 = 1:20

The maximum output variable error at 25 C is:

}

When two analogue input modules are connected (e.g. PSSu E F AI I) 1,0 %

}

When one analogue input module is connected (e.g. PSSu E F AI I) 3,6 %

Example:

}

Input current I

I0

 = 200 mA

}

Output current I

O0

 at R

1

 + R

2

 = 20 mA

}

Output current I

O1

 at R

2

 = 10 mA

I 0

O 0 +

O 1 +

0 V

O 0 -

O 1 -

I O1

I O0

I I0

R 1

R 2